2 2 |
Bosch Geothermal Heat Pumps
Bosch Thermotechnology Corp.
Data subject to change
Applications Manual
We nd that when looking at the Bosch three (3) ton
geothermal heat pump system cooling capacity at full
load, we see that at an Entering Fluid Temperature of
50°F (the typical shallow groundwater temperature for
the location is 47°F per Bosch Geo Solutions software)
and at 75°Fdb, 63°Fwb Entering Air Temperature (EAT)
(return air temperature), (typical ACCA load calculation
criteria for cooling), the total capacity of the unit is
38,680 Btu/h, with 28,140 Btu/h sensible capacity
(73% of total capacity). This leaves 10,540 Btu/h latent
capacity. The installer should meet 100% of both sensible
and latent capacity of the calculated cooling load. The
calculated sensible load is 24,000 Btu/h and this unit
provides 28,140 Btu/h. The latent load is 8,000 Btu/h
and this unit provides 10,540. Therefore, this Bosch
three (3) ton geothermal heat pump will comply with
typical sizing criteria selecting the unit to meet cooling
load requirements at summer design conditions for
Minneapolis, MN.
As the Bosch three (3) ton geothermal heat pump will not
be operating at the cooling outdoor design temperature
of 88°F except during the warmest summer days, the unit
will revert to low cooling or part load capacity most of the
cooling run time. Examining the actual bin hours for
Capacity Data - Part Load Cooling - all performance at 1000 CFM and 9.0 GPM
Entering
Fluid Temp.
(F)
Entering
Air Temp.
(F)
Total
Capacity
(MBtuH)
Sensible
Capacity
(MBtuH)
Sensible
to Total
Ratio
Power
Input
(kW)
Heat of
Reject
(MBtuH)
EER
50
70db
61wb
26.07
16.75
0.64
0.81
28.82
32.3
60
24.94
16.16
0.65
0.95
28.18
26.3
70
23.82
15.62
0.66
1.09
27.55
21.8
85
22.13
14.90
0.67
1.31
26.5
16.9
100
20.44
14.24
0.70
1.52
25.64
13.4
50
75db
63wb
27.94
20.05
0.72
0.81
30.71
34.4
60
26.74
19.35
0.72
0.95
29.99
28.0
70
25.53
18.71
0.73
1.10
29.28
23.2
85
23.73
17.85
0.75
1.31
28.21
18.1
100
21.92
17.07
0.78
1.53
27.14
14.3
50
80db
67wb
30.68
22.15
0.72
0.82
33.46
37.6
60
29.36
21.38
0.73
0.96
32.64
30.5
70
28.04
20.67
0.74
1.11
31.81
25.3
85
26.06
19.72
0.76
1.32
30.58
19.7
100
24.08
18.86
0.78
1.54
29.34
15.6
50
85db
71wb
33.42
24.28
0.73
0.82
36.22
40.6
60
31.98
23.43
0.73
0.97
35.29
33.0
70
30.55
22.65
0.74
1.11
34.35
27.4
85
28.39
21.61
0.76
1.33
32.94
21.3
100
26.24
20.67
0.79
1.55
31.54
16.9
Tab. 4
(EFT Range (Standard) 50F to 100F)
Содержание Geothermal Heat Pumps
Страница 1: ...Bosch Geothermal Heat Pumps For Residential Applications Applications Manual ...
Страница 2: ...2 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 126: ...126 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 127: ...Applications Manual Bosch Geothermal Heat Pumps 127 Bosch Thermotechnology Corp Data subject to change ...