Applications Manual Bosch Geothermal Heat Pumps
| 23
Bosch Thermotechnology Corp.
Data subject to change
Minneapolis, MN per the Bosch Geo Solutions software
program (see Table 5), the accumulated hours between
75ºF and 85ºF outdoor ambient is approximately 800.
Operating at part load during these temperatures will
improve humidity removal and still meet the structure heat
gain. If the outdoor temperature approaches the actual
cooling design temperature of 88°F, the Bosch three (3)
ton geothermal heat pump will shift to high cooling or full
load capacity to meet the structure cooling needs. At these
high outdoor ambient conditions, the Bosch three (3) ton
geothermal heat pump will meet approximately 97% of the
maximum limit, per ACCA Manual S.
Examining the part load speci cations (Table 4) for the
Bosch three (3) ton geothermal heat pump unit at 50°F
EFT (the typical shallow groundwater temperature for
the location is 47°F per Bosch Geo Solutions software),
we nd that at 75°Fdb, 63°Fwb Entering Air Temperature
(EAT) (return air temperature), the unit will produce a
total capacity of 27,940 Btu/h with 20,050 Btu/h sensible
capacity (72% of total capacity). This leaves 7,890 Btu/h
latent capacity.
Bosch Geo Solutions Software Data
Bin
(F)
Bin
Hrs
Bldg Load
(Btuh)
EWT
(F)
HPCap
(Btuh)
Run
Time
Pwr
(kW)
Auxillary
(kWh)
HP
(kWh)
Geo HW
(Btuh/yr)
Aux HW
(Btuh/yr)
Aux HW
(kWh
97
8
48000
59
40918
100%
2.12
20
17,746
0
0.00
92
50
39111
58
39111
100%
1.93
10
110,910
0
0.00
87
136
30222
57
30222
100%
1.20
152
301,677
0
0.00
82
285
21333
56
29944
71%
1.15
233
462,677
169,513
60.70
77
442
12444
54
30097
41%
1.13
206
405,859
574,589
205.76
72
613
3556
53
30250
12%
1.11
80
155,835
1,203,920
431.14
67
701
0
52
0
0
1,554,960
556.85
62
704
0
51
0
0
1,561,620
559.23
57
614
2407
50
25188
10%
2.69
0.00
100
275,335
1,086,64
389.14
52
552
6420
49
24922
26%
2.66
0.00
243
660,510
563,941
201.95
47
478
10432
47
24656
42%
2.64
0.00
345
930.051
130,253
46.64
42
487
14444
46
24390
59%
2.61
0.00
492
1,080,268
0
0.00
37
552
18457
45
24124
77%
2.59
0.00
719
1,224,452
0
0.00
32
653
22469
44
23858
94%
2.57
0.00
1046
1,448,491
0
0.00
27
591
26481
43
26481
100%
2.54
0.00
1351
1,310,962
0
0.00
22
475
30494
42
30494
100%
2.52
0.00
886
1,053,650
0
0.00
17
379
34506
40
31597
100%
2.49
328.64
946
840,701
0
0.00
12
313
38519
39
31017
100%
2.48
669.78
775
694,300
0
0.00
7
242
42531
38
30554
100%
2.46
863.88
595
536,807
0
0.00
2
190
46543
37
30091
100%
2.44
931.71
464
421,460
0
0.00
-3
131
50556
36
29627
100%
2.43
817.15
318
290,585
0
0.00
-8
81
54568
35
29164
100%
2.41
613.31
195
179,675
0
0.00
-13
45
58580
33
28700
100%
2.39
400.76
108
99,819
0
0.00
-18
16
62593
32
28237
100%
2.38
163.84
38
35,491
0
0.00
Tab. 5
During milder summer days, this Bosch three (3) ton
geothermal heat pump will run at part load and still
provide the necessary cooling needs for the structure,
meeting the majority of the heat gain at moderate outdoor
temperatures as well as the latent load. This operation
mode will require less electrical power to operate and will
enhance latent heat removal (dehumidi cation), resulting
in improved indoor temperature and air quality conditions
As the installation location is to be Minneapolis,
Minnesota, a colder climate, the installer should examine
the heating ability of the unit closely.
Содержание Geothermal Heat Pumps
Страница 1: ...Bosch Geothermal Heat Pumps For Residential Applications Applications Manual ...
Страница 2: ...2 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 126: ...126 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 127: ...Applications Manual Bosch Geothermal Heat Pumps 127 Bosch Thermotechnology Corp Data subject to change ...