Communication parameters
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Notification appliances
Standby
–
A-
–
B+
Alarm state
–
A-
–
B+
10 V to 15 V
0 V to 0.5 V
0 V to 1 V
21 V to 29 V
Inputs
–
Alarm resistor
820 ohm ±5%
–
EOL Resistor
3900 ohm ±1%
Zones (with resistance combination)
–
Alarm resistor
820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
–
EOL Resistor
3900 ohm ±1%
Zones (with EOL modules)
–
Alarm resistor
820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
6.1.1
Conventional Fire Panel
Technical Data | en
61
Bosch Sicherheitssysteme GmbH
2014.06 | 7.0 | F.01U.172.980