Notification appliance behavior in zone test
5
Press zone key 5.
This takes you to the Output Config menu.
1
Press zone key 1.
This takes you to the NAC submenu.
4
Press zone key 4.
This takes you to the NAC in test submenu.
2
1
...
Press zone keys 1 or 2.
1 Activation
2=No Activation (default setting)
Alarm Relay
In the Alarm Relay submenu, you can specify the properties of
the alarm relay. These include the Silencable and Drillable
settings. You can use Silencable to specify whether the relay
can be silenced manually. Drillable specifies whether the alarm
relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
Press zone key 5.
This takes you to the Output Config menu.
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
1
Press zone key 1.
This takes you to the Silencable submenu.
2
1
...
Press zone keys 1 or 2.
1 Silencable
2=Not Silencable (default setting)
4.5.2
Conventional Fire Panel
System Configuration | en
51
Bosch Sicherheitssysteme GmbH
2014.06 | 7.0 | F.01U.172.980
Содержание FPC-500-2
Страница 1: ...Conventional Fire Panel FPC 500 2 FPC 500 4 FPC 500 8 en Installation Guide ...
Страница 2: ......
Страница 81: ......