Alarm relay follows manual alarm
5
Press zone key 5.
This takes you to the Output Config menu.
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
2
Press zone key 2.
This takes you to the Drillable submenu.
2
1
...
Press zone keys 1 or 2.
1 Drillable
2= Not Drillable (default setting)
OC/Relay Extensions
In the OC/Relay Ext menu, you can individually set the
properties of all OC/Relay outputs. The possible settings for the
OC/Relay outputs 2 to 8 correspond to those for the first OC/
Relay . The following settings are possible:
–
Zone = Alarm: The output is activated if the zone triggers
an alarm. Here zone 1 is assigned to output 1, etc.
–
Zone Normal: If the zone is not in a normal state, the
output is activated. Assignment: zone 1 to output 1 etc.
–
Sum Alarm: When the fire panel is in an alarm state, this
output is activated regardless of the zone.
–
Sum PreAlarm: When the fire panel is in a pre-alarm state,
this output is activated regardless of the zone.
–
Sum Fault: This output is activated if there is a fault.
–
Sum Disable: If a fire panel element is disabled, this output
is activated (zones, notification appliances, relays).
–
Sum Test: This output is activated if a zone in the fire panel
is in test mode.
–
Not Used: The output is not used.
4.5.3
52
en | System Configuration
Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH