Possible zone dependencies:
–
FPC‑500-2: 1&2
–
FPC‑500‑4: 1&2, 3&4
–
FPC‑500‑8: 1&2, 3&4, 5&6, 7&8
If you set a zone to dual-zone dependency, the other associated
zone is also changed automatically.
Zones 1 to 8
3
Press zone key 3. This takes you to the Zone Config
menu.
1
Press zone key 1.
This takes you to the zone 1 submenu.
6
1
...
Use the zone keys to program the zone.
–
1=No Delay (default setting)
–
2 Int Alarm Stor
–
3 Alarm Verific
–
4 2-Det Depend
–
5 2-Zone Depend
Zones 2 to 8 are pre-programmed in the same way as zone 1.
You can change the settings as with zone 1.
Notice!
Zones 3 and 4 are only available on the FPC‑500‑4 and
FPC‑500‑8 panels. Zones 5–8 are only available on the
FPC‑500‑8.
Configuring Inputs
In the Input Config menu, you can program the behavior of the
inputs.
4.4
Conventional Fire Panel
System Configuration | en
47
Bosch Sicherheitssysteme GmbH
2014.06 | 7.0 | F.01U.172.980