Technical Data
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Zones
2
4
8
Max. number of detectors in
accordance with EN 54‑2
64
128
256
Max. number of detectors per
zone in accordance with
EN 54‑2
32
Max. number of extensions
0
1
2
Prog. inputs
1
2
AUX output
1
Alarm device output
2
Relay
2
Electrical Data
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Power supply voltage
230 VAC +10%/-15%, 50–
60 Hz
Current consumption
275 mA
312 mA
375 mA
AC power consumption
80 W
Operating voltage
21.4 VDC to 29 VDC
I
min
70 mA
I
max, a
0.7 A
I
max, b
2.3 A