Operation guide
Bosch Sicherheitssysteme GmbH
9.6
Triggering fire verification
9.6.1
Alarm verification
The transmission of the alarm is delayed. The alarm message must be checked to ensure it is
correct in the place where the detector generating the alarm is located.
An internal buzzer sounds on the panel. The signaling devices (e.g. sirens) and transmission
device to the fire department are not activated.
The time for checking the fire alarm is called the time to investigate. The duration of this time
can be different for every logical zone. The time to investigate is started if the fire alarm is
confirmed on the panel within the time to acknowledge.
If a real fire alarm is detected during the on-site inspection, the alarm must be forwarded to
the fire department; see
Section 9.6.3 Triggering alarm manually, page 47
. Alternatively, a
manual call point can be triggered at the location.
If it is a false alarm, the triggering detector can be reset or bypassed; see resetting alarm
message or bypassing detectors.
9.6.2
Starting time to investigate
If there is the possibility of testing, the following time spans are displayed. The counters
count to zero:
–
Time to acknowledge
The alarm must be confirmed within the specified time span.
–
Time to investigate
The alarm must be checked within the specified time span. This time
can be specified differently for each logical zone or detector.
–
Reset possible in
: time span after which the detector can be reset. For information on
resetting, see
Section 9.7 Resetting alarm message, page 47
.
To initiate alarm verification, select
Acknowledge
within the time shown to confirm the alarm.
The time to investigate will be displayed. The alarm verification is initiated.
Test the fire alarm onsite within the specified time.
CAUTION!
If another fire alarm is reported during the time to investigate, all alarm messages are
transmitted to the fire department. The time to investigate is canceled.
CAUTION!
Alarm messages from bypassed detectors are no longer displayed; only faults in these
detectors are displayed.
CAUTION!
The time to investigate is canceled if another alarm is reported within this time. Depending on
the configuration, all alarm messages are forwarded to the fire department in this case.
CAUTION!
If the time to acknowledge or the time to investigate is exceeded, the alarm is immediately
forwarded to external stations.
CAUTION!
If the alarm is not confirmed within this time, it will be forwarded to external stations.