Panel Controller
Maintenance | en
67
Bosch Sicherheitssysteme GmbH
Operation guide
F.01U.076.969 | 6.0 | 2010.04
14.5
Detector removal
To remove a detector:
1.
Select
Maintenance
from the start menu
2.
Remove detector
3.
Select
OK
to confirm the request. The following message appears:
All signaling and transmission devices will be inoperative for %d min
%d is used as a placeholder for the time that was defined in the FSP-5000-RPS
programming software, e.g. 15 minutes. The counter then counts from 15 minutes to zero
minutes. The detectors can be removed during this time.
To switch the signaling devices back on before the 15 minutes are up:
1.
Select
Restore manually disabled outputs
.
When the 15 minutes are up, the panel emits a brief signal tone and the start menu is
displayed.
14.6
Change device on V.24 Interface
On the V.24 interface, other devices can be optionally assigned in addition to a permanently
assigned device.
To assign a different device to the V24 interface:
1.
Select
Maintenance
from the start menu
2.
Change device at V.24 interface
A list of devices is displayed.
3.
Select the element you require in the display.
4.
Change the device on the V.24 interface.
The device is ready for operation.
14.7
Bypassing/Un-bypassing buzzer
In order to prevent an acoustic warning tone being sent to the panel during maintenance
work, for example, the panel's internal buzzer can be permanently bypassed.
To bypass the internal buzzer, select the following from the start menu:
1.
Maintenance
2.
Bypass buzzer
The buzzer is bypassed and the text on the user interface changes to
Unbypass buzzer
.
To un-bypass the buzzer again, select
Unbypass buzzer
in step 2.
NOTICE!
To remove a detector, all acoustic signals and transmission devices are bypassed for 15
minutes. They are automatically un-bypassed when the 15 minutes are up.
The acoustic signals can also be manually un-bypassed before the 15 minutes are up.
NOTICE!
After the system starts up following a power cut or battery failure, the permanently set-up
device is assigned to the V.24 interface again.
NOTICE!
If you switch the internal buzzer off permanently, no acoustic signal will sound on the panel in
the event of an alarm or fault!