background image

6720220330  Revised 05-12

19

ES SERIES

Operating Pressures & Temperatures

Environmentally Safe R-410A Refrigerant

This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system
charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid
temperatures below 50º assumes the use of antifreeze.

As a result of continuing research and development, specifications are subject to change without notice.

OPERATING DATA

COOLING

HEATING (+)

ENTERING

WATER

SUCTION

DISCHARGE

WATER

AIR

SUCTION

DISCHARGE

WATER

AIR

MODEL

WATER

FLOW

PRESSURE

PRESSURE

TEMP

TEMP

PRESSURE

PRESSURE

TEMP

TEMP

TEMP. ˚F

GPM

PSIG

PSIG

RISE ˚F

DROP ˚F

PSIG

PSIG

DROP ˚F

RISE ˚F

ES035

Full

Capacity

ES049

First
Step

ES049

Full

Capacity

30˚

40˚

50˚

60˚

70˚

80˚

90˚

100˚

30˚

40˚

50˚

60˚

70˚

80˚

90˚

100˚

30˚

40˚

50˚

60˚

70˚

80˚

90˚

100˚

4.5

74-90

244-299

3-4

13-15

9.0

78-95

251-306

2-3

13-16

4.5

122-149

183-224

14-18

19-23

87-106

257-314

4-5

15-18

9.0

117-143

172-210

8-10

20-24

91-111

263-322

3-3

16-19

4.5

131-160

214-261

14-18

18-22

164-201

269-329

5-6

17-20

9.0

126-154

201-245

8-10

19-24

173-211

276-337

3-4

18-22

4.5

136-166

244-298

14-17

18-22

111-136

282-344

6-7

19-23

9.0

131-160

230-281

8-10

19-23

117-143

289-353

4-5

20-24

4.5

141-172

275-336

14-17

17-21

124-152

294-360

7-8

21-25

9.0

135-165

258-316

8-10

18-22

131-160

302-369

5-6

22-27

4.5

145-178

310-378

14-17

17-20

136-166

307-375

8-9

23-28

9.0

140-171

291-356

8-10

18-22

143-175

314-384

5-6

24-30

4.5

150-183

349-426

14-17

16-20

149-182

319-390

8-10

25-30

9.0

144-176

328-401

8-9

17-21

156-191

327-400

6-7

26-32

4.5

155-189

392-480

13-16

16-19

9.0

149-182

369-451

8-9

17-21

4.0

64-78

248-303

5-6

15-18

6.0

67-82

254-311

3-4

16-19

4.0

109-134

183-224

18-22

19-23

75-91

261-319

6-8

17-21

6.0

105-128

172-210

10-12

20-25

79-96

267-327

4-5

18-23

4.0

118-144

214-261

18-22

19-23

142-173

273-334

8-10

20-24

6.0

113-138

201-245

10-12

20-24

149-182

280-342

5-7

21-26

4.0

122-149

244-298

17-21

18-22

96-117

286-349

9-11

22-27

6.0

117-143

230-281

10-12

19-24

101-123

293-358

6-8

24-29

4.0

126-154

275-336

17-21

18-22

107-131

299-365

11-13

25-30

6.0

121-148

258-316

10-12

19-23

113-138

306-374

7-9

26-32

4.0

130-159

310-378

17-21

17-21

117-143

311-380

12-15

27-33

6.0

132-153

291-356

10-12

18-22

123-151

319-390

8-10

29-35

4.0

134-164

349-426

17-20

17-20

128-157

324-396

13-16

29-36

6.0

129-158

328-401

9-12

18-22

135-165

332-406

9-11

31-38

4.0

139-170

392-480

16-20

16-20

6.0

133-163

369-451

9-11

17-21

6.0

71-87

277-339

6-7

15-19

12.0

75-92

284-347

4-5

16-20

6.0

118-144

194-237

21-25

19-23

84-102

291-356

7-9

18-22

12.0

113-138

182-223

12-14

20-24

88-108

299-365

5-6

19-23

6.0

127-155

226-276

21-25

18-22

159-194

305-373

9-11

20-25

12.0

122-149

213-260

12-14

19-24

167-204

313-383

6-7

21-26

6.0

131-160

259-316

21-25

18-22

108-132

320-391

10-13

23-28

12.0

126-154

243-297

12-14

19-23

113-138

328-400

7-9

24-29

6.0

136-166

291-355

20-25

17-21

120-147

334-408

12-15

25-31

12.0

130-159

273-334

12-14

18-22

126-154

342-418

8-10

27-32

6.0

140-171

328-401

20-24

17-20

131-161

348-425

14-17

27-34

12.0

135-165

308-377

11-14

18-22

138-169

356-436

9-11

29-36

6.0

145-177

369-451

20-24

16-20

144-176

362-442

15-18

30-37

12.0

139-170

347-424

11-14

17-21

151-185

371-453

10-12

32-39

6.0

149-183

415-508

19-24

16-19

12.0

143-175

391-477

11-14

17-21

Содержание FHP ES Series

Страница 1: ...ssure Regulating Valves 9 Cooling Tower Boiler Application 9 Earth Coupled Systems 10 System Checkout 10 Unit Start Up 10 Maintenance 10 Wiring Diagrams 14 Trouble Shooting 16 Unit Check Out 17 Operating Pressures Temperatures 18 MODEL NOMENCLATURE SERIES ES ENVIROSAVER AU AQUARIUS NOMINAL CAPACITY VOLTAGE DESIGNATION 1 208 1 60 230 1 60 3 208 3 60 230 3 60 SINGLE STEP ONLY CABINET CONFIGURATION V...

Страница 2: ...r maintenance operations on the system turn off main power to the unit Electrical shock could cause personal injury or death When working on equipment always observe precautions described in the literature tags and labels attached to the unit Follow all safety codes Wear safety glasses and work gloves Use a quenching cloth for brazing and place a fire extinguisher close to the work area LOCATION L...

Страница 3: ... the installation should be designed using current ASHRAE procedures for duct sizing If the unit is to be connected to existing ductwork a check should be made to assure that the duct system has the capacity to handle the air required for the unit application If the duct system is too small larger ductwork should be installed Check for existing leaks and repair The duct system and all diffusers sh...

Страница 4: ...r and control circuit Refer to the ELECTRIC HEATER PACKAGE OPTION section for wiring instructions minimum circuit ampacities and maximum fuse breaker sizing ECM INTERFACE BOARD THERMOSTAT CONNECTIONS Thermostat wiring is connected to the 10 pin screw type terminal block on the lower center portion of the ECM Interface Board In addition to providing a connecting point for thermostat wiring the inte...

Страница 5: ...proper jumper placement NOTE Always disconnect power before changing jumper positions on the interface board and reset the unit afterward To the left of the red and green status LED s is a row of 1 4 male quick connects These are used to pass thermostat inputs on to the rest of the control circuit Remember to always turn off unit power at the circuit breaker before attaching or disconnecting any w...

Страница 6: ...LINKS Low pressure lockout THREE BLINKS Freeze sensor lockout FOUR BLINKS Condensate overflow FIVE BLINKS Brownout Conditions The fault pulse code may be sent to the ALR fault terminal by placing the Alarm Output pin in the pulse position The pulse signal may be sent to a thermostat with a fault indication LED 24v and will display the fault code on the thermostat FREEZE SENSOR Optional freeze prot...

Страница 7: ...ITIAL POWER UP T ASC OR RS SEC TIME 30 SEC TIME 120 SEC COUNT 2 Start Timer Start Timer CC Output On CC Output Off Blink Code On Status LED Report Alarm Fault Hard Lockout ALR Output On Pulse Blink Code On Status LED Soft Lockout Record Alarm Start Counter If Applicable Start Anti Short Cycle Start Random Start Up Lockout Can Be Set To 4 Via Dip Switch Power Switchs Sensor Status Check 7 ...

Страница 8: ...he case of unit compressor and or compressor power supply failure See HP Series Heater Kit Instructions for field installations Each ES Series model has a number of heater sizes available Refer to Figure 9 for heater package compatibility with specific ES Series units models nomenclature and electrical data SEQUENCE OF OPERATION SINGLE STAGE UNITS Figure 13 Wire Schematic COOLING MODE Energizing t...

Страница 9: ...ake sure that the VA draw of the valve does not exceed the contact rating of the thermostat INSTALLATION OF PRESSURE REGULATING VALVES Pressure regulating valves are used to increase or decrease water flow through the heat pump in response to refrigerant pressure In some cases more water may be required in heating than in cooling or vice versa With the Envirosaver heat pumps these valves are not r...

Страница 10: ...stem switch to the OFF position The unit should stop running and the reversing valve should deenergize 6 Leave the unit off for approximately 5 minutes to allow for system equalization 7 Turn the thermostat to the lowest setting 8 Set the thermostat switch to HEAT 9 Increase the thermostat setting approximately 5 degrees above the room temperature 10 Verify the heat pump is operating in the heatin...

Страница 11: ...ONNECTION 3 LOW VOLTAGE CONTROL CONNECTION 4 LINE VOLTAGE CONNECTION 5 VIBRATION PAD 6 P T PORTS 7 HOSE KITS Optional 8 BALL VALVES 9 SOLENOID VALVE SLOW CLOSING 10 CONDENSATE DRAIN CONNECTION 11 PRESSURE TANK Optional 12 LINE VOLTAGE DISCONNECT ELECTRIC HEATER NOTE SEE FIGURE 3 FOR CONDENSATE DRAIN CONNECTION ES SERIES ...

Страница 12: ...E CONTROL CONNECTION 3 P T PLUGS Optional 4 HOSE KITS Optional 5 BALL VALVES 6 SUPPLY AND RETURN LINES OF CENTRAL SYSTEM 7 FLEX DUCT CONNECTION 8 HANGING BRACKETS ASSEMBLY 9 THREADED ROD 10 HANGING BRACKET ASSEMBLY ES048 and up 930 006 NOTE SEE FIGURE 3 FOR CONDENSATE DRAIN CONNECTION Figure 11 ES SERIES ...

Страница 13: ...TROL CONNECTION 4 LINE VOLTAGE CONNECTION UNIT 5 P T PORTS 6 VIBRATION PAD 7 CONDENSATE DRAIN 8 GROUND LOOP CONNECTION KIT 555 000 001 9 GROUND LOOP PUMPING PACKAGE GL001 1 or 002 1 10 POLYETHELENE WITH INSULATION 11 LINE VOLTAGE DISCONNECT ELECTRIC HEATER NOTE SEE FIGURE 3 FOR CONDENSATE DRAIN CONNECTION Figure 12 ES SERIES ...

Страница 14: ...6720220330 Revised 05 12 14 ES SERIES Figure 13 ...

Страница 15: ...6720220330 Revised 05 12 15 Figure 14 ES SERIES ...

Страница 16: ...arge The unit is overcharged with refrigerant Reclaim refrigerant evacuate and recharge with factory recommended charge High pressure Check for defective or improperly calibrated high pressure switch UNIT OFF ON LOW PRESSURE CONTROL Suction pressure too low In COOLING mode Lack of or inadequate air flow Entering air temperature too cold Blower inoperative clogged filter or restrictions in ductwork...

Страница 17: ...__ Entering Leaving Fluid Temp _______________ _______________ _______________ _______________ Compressor Volts Amps _______________ _______________ _______________ _______________ Blower Motor Volts Amps _______________ _______________ _______________ _______________ Fluid Flow gpm _______________________________ _______________________________ Fluid Side Pressure Drop ___________________________...

Страница 18: ... 7 9 28 33 2 147 179 357 437 13 16 16 18 149 181 345 422 12 14 29 35 4 141 172 335 411 7 9 17 20 156 190 352 432 8 10 31 37 2 151 185 402 492 13 15 15 18 4 146 177 378 459 7 9 16 19 4 76 92 242 297 3 4 13 14 6 80 97 249 304 2 3 13 15 4 125 151 180 221 14 18 19 22 89 108 255 312 4 5 15 17 6 120 146 169 207 8 10 20 23 93 113 261 320 3 3 16 18 4 134 163 211 258 14 18 18 21 106 118 267 327 5 6 17 19 6...

Страница 19: ...9 426 14 17 16 20 149 182 319 390 8 10 25 30 9 0 144 176 328 401 8 9 17 21 156 191 327 400 6 7 26 32 4 5 155 189 392 480 13 16 16 19 9 0 149 182 369 451 8 9 17 21 4 0 64 78 248 303 5 6 15 18 6 0 67 82 254 311 3 4 16 19 4 0 109 134 183 224 18 22 19 23 75 91 261 319 6 8 17 21 6 0 105 128 172 210 10 12 20 25 79 96 267 327 4 5 18 23 4 0 118 144 214 261 18 22 19 23 142 173 273 334 8 10 20 24 6 0 113 13...

Страница 20: ...16 20 18 22 143 175 385 471 12 15 33 41 7 0 122 149 321 392 11 13 18 22 152 186 393 480 9 11 35 43 5 0 128 157 378 462 16 19 17 21 7 0 125 152 353 432 11 13 18 22 7 0 68 84 256 313 5 7 19 23 14 0 73 89 261 319 4 5 20 25 7 0 117 143 182 222 15 19 21 26 81 99 277 339 7 8 22 26 14 0 114 139 170 208 11 14 22 27 86 105 283 346 5 6 23 28 7 0 120 147 215 263 15 18 20 25 93 114 299 365 8 9 24 29 14 0 117 ...

Страница 21: ...64 351 429 13 16 18 22 146 178 388 474 12 15 33 41 16 0 131 159 329 401 10 12 19 23 155 189 396 483 9 11 35 43 10 0 137 167 385 469 12 15 17 21 16 0 134 163 360 439 9 11 18 22 3 0 68 83 243 297 6 7 14 17 5 0 76 92 253 309 3 4 15 18 3 0 133 162 171 209 17 21 18 22 83 101 255 312 7 9 16 20 5 0 128 156 155 190 10 13 19 23 92 113 266 325 4 5 17 21 3 0 135 165 205 251 17 20 17 21 98 119 268 327 9 11 19...

Страница 22: ...13 16 16 19 147 179 347 424 12 14 29 36 7 5 138 169 338 414 7 9 17 21 154 188 355 434 8 10 31 38 3 5 149 182 405 495 13 15 15 19 7 5 143 174 381 465 7 9 16 20 4 5 74 90 244 299 3 4 13 15 9 0 78 95 251 306 2 3 13 16 4 5 122 149 183 224 14 18 19 23 87 106 257 314 4 5 15 18 9 0 117 143 172 210 8 10 20 24 91 111 263 322 3 3 16 19 4 5 131 160 214 261 14 18 18 22 164 201 269 329 5 6 17 20 9 0 126 154 20...

Страница 23: ...170 347 424 11 14 17 21 151 185 371 453 10 12 32 39 6 0 149 183 415 508 19 24 16 19 10 0 143 175 391 477 11 14 17 21 8 0 68 84 256 313 5 7 19 23 12 0 73 89 261 319 4 5 20 25 8 0 113 138 172 210 18 22 19 23 81 99 277 339 7 8 22 26 12 0 110 134 161 196 12 14 20 24 86 105 283 346 5 6 23 28 8 0 116 142 206 252 17 21 19 23 93 114 299 365 8 9 24 29 12 0 112 137 193 236 12 14 19 24 99 121 305 373 6 7 25 ...

Страница 24: ...6720220330 Revised 05 12 601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www boschtaxcredit com www fhp mfg com ...

Отзывы: