E 24 V– Digital Input Modules
6–4
1070 072 145-102 (01.07) GB
V / I characteristic curve, as per EN 61131-2
30 V
20 V
0 V
10 V
0 mA
5 mA
10 mA
15 mA
HIGH signal
LOW signal
Switchover range
Actual
switchover range
U
I
Addressing
A start address must be set for each module on the S1 DIP switch (example
below is for an E 24 V–, 32-way):
S1 DIP switch
Start address
Pos. W = Word consistency
Pos. B = Byte consistency
(factory preset position)
Jumper must be in place.
W
B
The DIP switch elements S1 through 8 are used to select between input I and
extended input field EI.
Switch
8
7
6
5
4
3
2
1
Weighting
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Value
I = OFF
EI=ON
64
32
16
8
4
2
1
Содержание CL200
Страница 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Страница 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Страница 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Страница 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Страница 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Страница 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Страница 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Страница 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Страница 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Страница 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...