Installation
17–12
1070 072 145-102 (01.07) GB
As regards the application of the Directive, a largely comprehensive over-
view was provided in the “Guidelines on the application of Council Directive
89/336/EEC of May 1989 on the approximation of the laws of the Member
States relating to electromagnetic compatibility”, which was, in its release
dated 23 May 1997, published by the European Commission.
Radiant emittances, radio interference
The CL200 meets the requirements of the generic EN 50081-2 standard
which defines the limit values for interference emissions. This standard ap-
plies exclusively to application in industrial areas. In contrast to residential
areas, application in industrial areas is characterized by the following sti-
pulations:
D
Connection to the public low-voltage mains network is not permitted.
D
Enterprise-owned high or medium voltage transformer is available.
D
Operation occurs in an industrial environment or in the vicinity of indu-
strial power grids.
The term “industrial area” bears no relevance to the separation of industrial
and residential zoning on the basis of the planning and building laws and re-
gulations of some countries.
The limit values for industrial applications are higher than those governing
application in a residential area. For this reason, in anticipation of the deploy-
ment of this equipment in a residential area, the user is required to introduce
certain additional measures:
D
Installation of the controller system in a control cabinet and/or a housing
providing a high degree of screening attenuation.
D
To meet the requirement of reduced emission values, all cables exiting
the screened area (e.g., control cabinet) must be provided with filter and
screening measures.
For system application within a personal residence, in business areas, on
retail premises or in a small-industry setting, the user will be required to ob-
tain a single operating license issued by the appropriate national authority or
approval body.
Protection against electrostatic discharges
All modules belonging to the CL200 controller system contain components
that may be destroyed as a result of electrostatic discharges (ESD). It should
be noted that a defect inflicted on a module must not necessarily be recogni-
sable immediately. Instead, it may manifest itself through occasional or de-
layed unit failures.
For this reason, the standard procedures for handling electronic compo-
nents and assemblies must be strictly observed. It is specifically prohibited
to remove or connect plug connectors on a live unit. Before touching or gras-
ping a module, the respective person must ensure that he or she is electro-
statically discharged.
Содержание CL200
Страница 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Страница 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Страница 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Страница 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Страница 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Страница 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Страница 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Страница 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Страница 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Страница 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...