NT200 Power Supply Module
4–7
1070 072 145-102 (01.07) GB
L
Remove old backup battery.
This causes a battery warning to be indicated in the system area and on the
programming device.
L
Gently tap new backup battery on hard surface to break internal oxide layer.
L
Ensuring correct polarity, insert new battery.
L
Reinstall battery compartment cover, and push upward.
L
To cancel the battery warning, press the Battery Reset button on the front
panel of the NT200 power supply module.
.
The old backup battery (lithium battery) must be disposed of as hazar-
dous waste (i.e., in Germany under waste code number 35 325). The ac-
ceptance provisions of the disposal site must be observed.
4.4
Specifications
Specifications
NT200
Power supply, as per EN 61131-2
24 VDC, 19.2 through 30 V
Bridging capability, intermittents on power
supply module, as per EN 61131-2
Class PS2
v
10 ms,
repetition rate
w
1 s
Current draw from 24 V power supply
D
Rated current
1.8 A
D
Minimum configuration: NT200,
ZE200A, 16 inputs, 16 outputs
typ. 220 mA
Peak inrush current
v
40 A
Duration of peak inrush current
v
5 ms
Power supply, voltage rated, for
D
Central processing unit
D
Memory backup
D
Peripheral modules
D
20mA interface
5 V
3.4 V
7.5 V
12 V ISO
Power supply, current rated
D
5 V for central processing unit
and intelligent modules
D
7.5 V for peripheral modules
D
12 V ISO for 20mA interface
max. 2.7 A
1.5 A
max. 150 mA
Memory backup battery
D
Type
D
Capacity
D
Battery voltage
D
Effective service life
Lithium battery
AA
w
850 mAh
3.6 V
1 year (minimum)
Width
1 slot
Weight
400 g
Содержание CL200
Страница 3: ...Antriebs und Steuerungstechnik CL200 Manual CL200 102 Edition ...
Страница 8: ...Contents VIII 1070 072 145 102 01 07 GB Notes ...
Страница 24: ...System Introduction 2 8 1070 072 145 102 01 07 GB Notes ...
Страница 38: ...Module Racks 3 14 1070 072 145 102 01 07 GB Notes ...
Страница 82: ...E 24 V Digital Input Modules 6 6 1070 072 145 102 01 07 GB Notes ...
Страница 104: ...Digital Input Output Modules 8 10 1070 072 145 102 01 07 GB Notes ...
Страница 110: ...DP EA4 Peripheral Bus Station Module 9 6 1070 072 145 102 01 07 GB Notizen ...
Страница 114: ...AG S Expansion Module 10 4 1070 072 145 102 01 07 GB Notizen ...
Страница 122: ...R200 R200P COM2 E Communication Modules 11 8 1070 072 145 102 01 07 GB Notizen ...
Страница 158: ...Appendix A 4 1070 072 145 102 01 07 GB Notes ...