AVIOTEC IP starlight 8000
Adjustment of detection settings | en
33
Bosch Sicherheitssysteme GmbH
Operation and Commissioning Manual
2020.08 | 01 | F.01U.391.015
7
Adjustment of detection settings
The standard settings of the video-based fire detection will be sufficient for the most
customer environments. Nevertheless, there are many ways to adapt the flame and smoke
detection to the requirements of the customer. The detection settings of the fire detection
can be changed in the configuration menu:
1.
Go to
Configuration
and navigate to
Alarm
.
2.
Select
Fire detection
.
Notice!
The VCA settings affect the Fire detection settings.
You can create three individual profiles for Fire detection. These different Fire detection
profiles can also be used in a scheduled configuration (see Setting up VCA):
–
Silent VCA
–
profile #1 (renameable in VCA settings)
–
profile #2 (renameable in VCA settings)
General and special settings for
Fire detection
are selectable. Anytime you change the
settings, confirm with
Set
to apply these changes.
If you want to abort, just click on another menu option, for example
Audio Alarm
.
The Intelligent Video Analytics functions and the video-based fire detection settings can be
changed during operation and will immediately become effective.
7.1
General settings
Following settings change the detection algorithm generally.
Flames
The default setting of the flame size is 1.1% of the picture width.
Verification time [s]
of the flame detection can be set to 4, 8, 12 or 16 seconds. The default
value is 8 seconds. Small values cause faster detection (higher risk of false alarms), larger
values decrease false alarms.
Smoke
The default setting of the smoke size is 1.6% of the picture width.