FPA‑5000 | FPA‑1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000

FPE‑8000‑SPC | FPE‑8000‑PPC | FPE‑2000‑SPC | FPE‑2000‑PPC |
FPE‑8000‑FMR

en

User Guide

Содержание AVENAR 8000

Страница 1: ...FPA 5000 FPA 1200 AVENAR panel 8000 AVENAR panel 2000 AVENAR keypad 8000 FPE 8000 SPC FPE 8000 PPC FPE 2000 SPC FPE 2000 PPC FPE 8000 FMR en User Guide ...

Страница 2: ......

Страница 3: ...ay support information 19 5 Operating principle 20 5 1 Switch on and switch off 20 5 2 Initial setup 21 5 3 Logging on and off 22 5 3 1 Logging on 22 5 3 2 Logging off 22 5 4 Access authorization 22 5 5 Calling up the start menu 23 5 6 Personalized menu 23 5 7 Selecting the menu 23 5 8 Returning to the previous selection 23 5 9 Working with lists 24 5 9 1 Scrolling through lists 25 5 9 2 Various s...

Страница 4: ...a message 41 9 4 Silence internal buzzer 41 9 5 Activate and silence signaling devices 41 9 6 Resetting signaling devices and transmission devices 41 9 7 Triggering fire verification 42 9 7 1 Alarm verification 42 9 7 2 Starting time to investigate 42 9 7 3 Triggering alarm manually 43 9 8 Resetting alarm message 43 9 9 Bypassing detectors 44 10 Fault message 45 10 1 Calling up fault indication 45...

Страница 5: ...3 4 2 CAN Bus 58 13 5 Panel Passport 58 13 6 LED Test on modules 58 13 7 Network services 58 13 7 1 Routing table 58 13 7 2 Consistency check 59 13 7 3 Ethernet ports 59 13 7 4 Send ping command 60 13 7 5 Remote services 60 13 8 Voice alarm systems 61 14 Maintenance 63 14 1 Menu overview 63 14 2 Change language 63 14 3 Activate Outputs 63 14 4 Activate Transmission Device 64 14 5 Bypassing Un bypa...

Страница 6: ... 5 2 Change universal password 78 18 5 3 Set Default Password 78 18 6 Rename elements 78 18 7 Network services 79 18 7 1 Ethernet 79 18 7 2 Change date time 79 18 7 3 Remote Services 79 18 8 Overview 79 19 Further functions 81 19 1 Menu overview 81 19 2 Change Date Time 81 19 3 Master password 81 19 3 1 Enter the master password that is valid indefinitely 81 19 3 2 Enter the 24 hour master passwor...

Страница 7: ...ke if a fire breaks out The user guide is a statutory part of the system and must be made known to the new owner if the system is ever sold Notice The personal access code consisting of user ID and password must not be made known to third parties Warning The device must be shut down by power button Don t unplug the device from power supply while the system is in operation This could result in the ...

Страница 8: ...ocking and resetting elements Monitoring and controlling of sounders and outputs Performing a walktest Display diagnostic information about every LSN element Configuration of detectors short texts and detector sensitivity Performing a drill Saving displaying and printing out events Switching the system to day or night mode Notice The manual control of evacuation zones and the outputs connected to ...

Страница 9: ...unctions at a glance page 11 2 1 What is new The AVENAR panel 8000 2000 is the successor panel of the FPA 5000 FPA 1200 modular fire panel AVENAR panel 8000 2000 combines a new and powerful panel controller platform with all the well known stable safety features When operating the AVENAR panel 8000 2000 please note the following important innovations Physical node address PNA RSN The physical node...

Страница 10: ... cut or battery failure the default language set in the FSP 5000 RPS is displayed again 2 5 Warranty and liability Warranty and liability claims for personal and property damage are excluded if these were caused by one or several of the following causes Use of the fire panel contrary to the regulations Improper set up installation start up operation or maintenance Disregarding of the user manual S...

Страница 11: ...ect by number Bypass buzzer Printer NAC Transmission device HVAC Doorholder Detector Logical zone Extinguishing system Annunciator Bypass Block group More Control element Interface module Diagnostics Diagnostics Element details Modules Hardware Panel passport LED test on modules History log Network services VAS Maintenance Maintenance Walktest Change language Activate outputs Activate transmission...

Страница 12: ...User Guide Bosch Sicherheitssysteme GmbH Further functions Further functions Change date time Master password Remote Services Change password Drill Alarm counters Control Monitoring Activate doorholder Activate HVAC Activate control element Search function Go to element Reset Reset Event type Scope Logical zone Detector This panel ...

Страница 13: ... GHI JKL MNO 7 8 9 PQRS TUV WXYZ 0 F1 F2 F3 _ 1 Status LEDs 6 Display a list of the networked panels and establish a remote connection with a networked panel 2 Information bar 7 Display and control all alarm zones 3 Status bar 8 Log in to the panel and call up personalized menu 4 Open start menu 9 Silence internal buzzer 5 Go back 10 Function keys programmable 11 Display support information 4 1 Op...

Страница 14: ...rapidly through lists Enter key Confirm an alphanumeric entry Confirm an entry that is not confirmed by selecting the OK field on the touch screen Alphanumeric keypad Entry of letters special characters and numbers Function keys There are three function keys F1 F2 and F3 which are freely programmable with frequently used functions of the panel via the Programming Software If a function key is acti...

Страница 15: ... System panel fault G System in operation R Programmable LED for a self defined alarm Y Programmable LED for a self defined fault diasablement Y yellow R red G green blinking fault steady disabled The LEDs for the status of devices like detectors signaling devices alarm transmission devices and the outputs to fire protection equipment always light up in combination with the general fault or genera...

Страница 16: ...ce disabled and in fault status Notice As neither the panel nor the power supply can have the status disabled the system fault and the power fault icon light up steadily in yellow in the status fault 4 3 Touch screen Caution Do not use any pointed or sharp objects e g screw drivers pens etc when operating the touch sensitive display The touchscreen may not be exposed to direct sunlight Both can se...

Страница 17: ...ration keys 2 Menu field 5 Alphanumeric keyboard 3 Status bar 6 Function keys programmable Information bar The information bar displays general information as text or icons Icon Meaning No connection established Only displayed on the panel No connection established Only displayed on the keypad Remote connection established Operator has restricted use of the remote panel no control only monitoring ...

Страница 18: ...iggered a fire alarm Control Elements that are activated Fault Elements that have reported a fault Bypass Disabled elements In addition it is possible to display an overview of the type and nature of all message types received by the panel Status Display of a list of the various message and status types and the number of elements in the respective state To display the individual elements touch the...

Страница 19: ...layed In a networked fire detection system further icons can be displayed in the standby display depending on the network setting 4 5 Display support information To display the address of the company providing the support please press the company logo in the upper right corner of the panel screen DEF 2 1 ABC 3 4 5 6 GHI JKL MNO 7 8 9 PQRS TUV WXYZ 0 F1 F2 F3 _ Notice Information concerning support...

Страница 20: ...n are Press once shortly Start the panel Press once shortly at a running panel Shut down the panel Notice A confirmation sound is played when the shutdown sequence is starting The shutdown is completed when the general fault and the system panel fault status LEDs light up Wait until the shutdown is completed before you interrupt the power Notice After having shut down the panel please interrupt th...

Страница 21: ... instructions on the screen The boot process will automatically continue after the calibration was completed Set time and date Touch the field you require and enter the correct value For details see Change Date Time page 81 Set physical node address PNA RSN You must set the physical node address PNA RSN when switching on the panel for the first time Notice There are no mechanical rotary switches T...

Страница 22: ... text page 27 for information on how to enter numbers 2 Enter your password in the second field Notice The default password is 000000 For security reasons please change this password see Change password page 83 3 Select OK to confirm the entries or Cancel to cancel the operation Refer to Change password page 83 for information on how to set up your own password The standby display is shown As long...

Страница 23: ...menu element to the standby display if no entries are made after 5 minutes in case of an alarm or a fault message after 60 minutes see also Standby screen page 18 If the screen is black touch it gently to display the standby screen 5 6 Personalized menu Via the FSP 5000 RPS programming software you can configure your personalized start menu which displays up to eight functions you need most often ...

Страница 24: ...iption in alphabetical order address allocation also given By number sorted in ascending order by number logical or physical address description also given By number no description shown by number logical or physical address in ascending order the numbers are displayed in number blocks and the description is not given This list is only offered when detectors and logical zones are being selected Ex...

Страница 25: ... particular place To jump to the beginning of a list touch To jump to the end of a list touch 5 9 2 Various states of list fields Various states can be assigned to an element or an element group depicted by a list field The following table provides information about the possible states List field State of list field Meaning TEXT normal Element in normal state TEXT marked Selected element TEXT Mode...

Страница 26: ...have an additional selection option see Displaying and un bypassing bypassed element groups 5 10 Search Function Element In lists a particular element can be searched for and displayed using the search screen The following search criteria are offered By description The element is searched for in the list by its description By number The element is searched for in the list by its number In some men...

Страница 27: ...ntry of another number is possible a second search window is displayed Notice If you are not offered another field there is no element with the addressing you have searched for 3 Enter the next digit and confirm your entry with the Enter key 4 If necessary enter further digits until the number is shown in full You must confirm each entry with the Enter key The list field of the element you are sea...

Страница 28: ...te the marked number press the key with the required number until the number you require is displayed in the search screen 5 11 2 Deleting all numbers 1 In order to delete all numbers in the search screen press the left arrow key until the cursor marks the first number 2 Enter a new number using the number pad All numbers up to the digit entered are deleted 3 If you wish to continue entering the n...

Страница 29: ... of the start menu To do this press the double arrow key on the keypad 5 14 Standby When the touchscreen is not operated its backlight switches off after 5 minutes Notice In case of an active alarm or fault message the backlight switches off after 60 minutes The display switches back to this message from any other element of the menu after 30 seconds If the screen is black touch it gently to displ...

Страница 30: ...dify the values using the number keys on the alphanumeric keypad Or Touch the Change field Touch the field containing the number block to be changed Use the arrow keys on the operating panel to select the desired numbers and modify the values using the number keys on the alphanumeric keypad Touch OK to apply the changes or Cancel to discard the changes You are returned to the initial Configuration...

Страница 31: ...tion from FSP 5000 RPS corresponds to the configuration entered at the panel controller In the event of discrepancies a fault message is displayed Ethernet redundancy Information concerning redundancy The RSTP parameters of the RSTP panel and those of the root bridge are displayed Remote Services Information concerning the features and the status of the Remote Services Further information can be f...

Страница 32: ...ich an operator who is logged in to the panel controller is logged out 7 2 Connecting to remote panel Through the remote keypad it is possible to establish a connection to a remote panel 1 Press The display shows a list of available network nodes 2 Select a node and press OK 3 Press again OK P The connection to the remote panel is established Depending on the type of connection a symbol is display...

Страница 33: ...VENAR panel 2000 AVENAR keypad 8000 Remote keypad en 33 Bosch Sicherheitssysteme GmbH User Guide 2020 07 3 0 F 01U 378 877 Closing the connection to remote panel 1 Press 2 To confirm press Yes P The connection to the remote panel is closed ...

Страница 34: ...es of alarm On the panel controller a distinction is made between the following types of alarm Fire Heat Smoke Water Supervisory Depending on the configuration external transmission devices e g fire department notification appliances e g sirens and or strobes and fire protection systems e g sprinkler systems fire doors are activated Notice If an alarm delay is set for the detector triggering the a...

Страница 35: ... detector dependency then this is displayed on the system as a pre alarm The transmission device to the fire department is not activated The detector generating the alarm is reset after the first signal The pre alarm becomes the main alarm if a second detector in the same logical zone triggers an alarm The transmission devices and notification appliances are activated Dual zone dependency If a det...

Страница 36: ... 4 1 Optical and acoustic signals The LED alarm icon lights up red An internal buzzer sounds see also Silence internal buzzer page 41 Depending on the configuration sounders and or visual notification appliances e g sirens strobes are activated If the transmission device to the fire department is activated the LED icon lights up red 8 4 2 Displaying the detector zones in alarm state The number of ...

Страница 37: ...et all of the alarm messages shown on the display see also Resetting alarm message 8 4 3 Sequence of the alarm messages The messages are displayed in chronological order The newest alarm message of a logical zone is always displayed at the end of the list The first and oldest alarm message of a logical zone is displayed at the beginning of the list The next three messages are displayed as you scro...

Страница 38: ...t message The latest message is always displayed at the end of the list The message number e g 008 of the latest message indicates the total number of logical zones in which one or more detectors have triggered an alarm 8 4 6 Displaying the individual detectors in a logical zone To display the individual detectors in a logical zone select the logical zone you require The alarm messages for the ind...

Страница 39: ...ne such as the installation location of the detector or the detector type To display more information about an alarm message see Displaying additional information 8 4 8 Displaying additional information Notice By way of example an action text can be entered for every detector type in the FSP 5000 RPS programming software To display further information about the individual detectors select the alar...

Страница 40: ... the Alarm LED icon An internal buzzer sounds on the system Notice Alarm messages have the highest priority compared with all other message types If a fire alarm is reported the system switches automatically to alarm indication 9 1 Evacuation You can manually control all available evacuation zones Press the evacuation button to open the list with all available evacuation zones To search for a spec...

Страница 41: ...ect a message and then press Acknowledge Only the selected message is acknowledged Notice If Go to Acknowledge is displayed select this field in order to display the messages that have not yet been acknowledged 9 4 Silence internal buzzer Press the following key to temporarily silence the internal buzzer The internal signal tone is silenced 9 5 Activate and silence signaling devices Sounders and o...

Страница 42: ...alarm is confirmed on the panel within the time to acknowledge Caution If another fire alarm is reported during the time to investigate all alarm messages are transmitted to the fire department The time to investigate is canceled If a real fire alarm is detected during the on site inspection the alarm must be forwarded to the fire department see Triggering alarm manually page 43 Alternatively a ma...

Страница 43: ...uring the check a real fire alarm is detected then this alarm to the panel must be manually forwarded to external stations such as the fire department Alternatively a manual call point can be triggered at the location 1 To forward the alarm to external stations select Manual alarm 2 Select OK to confirm the operation The alarm is forwarded to the fire department In the LED display the icon turns r...

Страница 44: ...he menu items Zone and Detector a list with all the logical zones and detectors concerned appears 2 Select the list field you require Refer to Scrolling through lists page 25 for information on how to scroll forward and backward through a list The list field is marked 3 Select Reset The selected element element group is reset TEXT R If a list field is marked with an R the process of resetting is n...

Страница 45: ...messages grouped by message type is displayed The number of elements is also given in each case To display the fault messages select the message category you require in this case Fault 0 Fire 0 Control 8 Fault 0 Bypass Status Caution If a message does not have to be reset it is removed from the display as soon as the fault has been rectified Notice If individual elements that are combined with oth...

Страница 46: ...the element group Number of individual elements that have caused a fault in the respective element group Message number Additional information e g the installation location Example Fault Zone 00005 001 Office 1 6 Element category Different detectors in one logical zone Message type Fault Address of element groups 00005 The fifth logical zone caused the first fault Number of individual elements 6 I...

Страница 47: ...ocation Example Fault Transmission device 00026 004 002 Cafeteria Element category Transmission device Message type Fault Element address The following transmission device has caused a fault 00026 004 The fourth transmission device 004 in the 26th group 00026 Message number The fault messages are numbered chronologically The message number in the second line indicates the sequence in which the fau...

Страница 48: ...power LED steady Fault detector LED blinking Fault transmission device LED blinking Fault signals LED blinking Output to fire protection equipment fault LED blinking Acoustic signal An internal signal tone sounds on the system To temporarily silence the internal buzzer Press 10 3 Resetting fault message Caution If a message does not have to be reset it is removed from the display as soon as the fa...

Страница 49: ...User Guide 2020 07 3 0 F 01U 378 877 10 4 Blocking an element In order to block an element that has caused a fault 1 Select the fault message you require 2 Select Block Caution The system does not transmit any information as to whether it was possible to block the selected element To monitor the operation check the element ...

Страница 50: ... Annunciator Bypass group More Control element Interface module 11 2 Bypassing and un bypassing elements Select the element you require in the submenu Notice Partly bypassed elements such as loops or bypass groups can be displayed and completely bypassed see Displaying and un bypassing bypassed element groups page 50 Notice The menu structure may be different depending on the configuration in FSP ...

Страница 51: ...mber displays the number of bypassed elements or element groups in the relevant element category 4 Select the element category you require e g Detector A list of all bypassed detectors is displayed To un bypass bypassed elements 1 Select the element you require 2 Select Un bypass The element is un bypassed 11 4 2 Via the status bar To display a list of all bypassed elements 1 Select Bypass from th...

Страница 52: ...elay in the FSP 5000 RPS configuration and press the Enter key A list of various states is displayed 5 Select the output to fault warning routing equipment from the list and press Bypass If necessary enter your user ID and password to log on to the panel controller The output to fault warning routing equipment is bypassed 11 6 2 Un bypassing the output to fault warning routing equipment There are ...

Страница 53: ...h Sicherheitssysteme GmbH User Guide 2020 07 3 0 F 01U 378 877 3 Select the output to fault warning routing equipment from the list and press Un bypass If necessary enter your user ID and password to log on to the panel controller The output to fault warning routing equipment is un bypassed ...

Страница 54: ...le To block a detector select the following in the start menu 1 Bypass Block 2 Block 3 Detector Various selection criteria are displayed See also Working with lists page 24 4 Select a selection criterion e g By description A list of the detectors is displayed Refer to Scrolling through lists page 25 for information on how to scroll forward and backward through the list 5 Select the required list f...

Страница 55: ...ors is displayed To unblock elements 1 Select the element you require 2 Select Un block The element is unblocked 12 3 2 Via the status bar To display a list of all blocked elements 1 Select Bypass from the status bar A list of various states is displayed 2 Select Blocked A list of various element categories is displayed The listed figure indicates the number of blocked elements or element groups i...

Страница 56: ... Hardware Panel passport LED test on modules History log Network services VAS 13 2 Element details To display diagnostic information about the elements in a particular module 1 In the start menu select Diagnostics 2 Element details A list of the LSN modules is displayed Notice The numbers before the module names indicate the slot of the module on the panel 1 Select the list field you require On th...

Страница 57: ...all used modules is displayed 4 Select the list field you require A list of various information options is displayed Module passport Module Compatibility Module status For an LSN module the following selection fields are also offered Module status and counters Reset counters 5 Select the information option you require e g Module status Diagnostic information about the module status is displayed A ...

Страница 58: ...version Build type Build number Serial number MAC Address 13 6 LED Test on modules To test the LED display of selected modules 1 In the start menu select Diagnostics 2 LED test on modules A list of various selection criteria is offered Select LED test all modules to test the LED display of all modules Select By number or By type to test the LED display of individual selected modules Example To tes...

Страница 59: ... 64 can be assigned to panels 13 7 2 Consistency check Inconsistencies between the network settings configured in FSP 5000 RPS and those set in the panel controller are displayed under Diagnostics Network services Consistency check 1 In the start menu select Diagnostics 2 Network services 3 Consistency check Where inconsistencies are identifiable between the network settings saved in the panel con...

Страница 60: ...select the desired number and modify using the number keys on the alphanumeric keypad If the addressed network node is accessible a success message is displayed 13 7 5 Remote services Remote Services offer a secure remote internet connection to AVENAR panel 8000 2000 for system integrators The following features are available Remote Maintenance Remote Connect Remote Alert For these services the se...

Страница 61: ...mote ID please see Remote Services System ID identifies one AVENAR panel 8000 2000 system representing one FSP 5000 RPS configuration It is assigned to the panel by the RemotePortal server Status of Remote services Shows if a remote connection to the RemotePortal server is configured Enabled Disabled Connection state Only available at the panel which is configured as gateway panel Shows if the con...

Страница 62: ...sts Status of VAS over IP In case of trouble please check the VAS over IP Trigger configuration Mismatch A VAS Virtual Trigger programmed in the AVENAR panel 8000 2000 configuration cannot be matched to an equivalent trigger on the VAS over IP side Please check the mapping of the virtual VAS triggers virtual control inputs configured in the FSP 5000 RPS programming software and the VAS over IP con...

Страница 63: ... a shortcut see Changing language display page 28 Notice After the system starts up following a power cut or battery failure the default language defined in the FSP 5000 RPS programming software is set again Making a selection via the menu 1 In the start menu select Maintenance 2 Change language A list of the languages which can be selected is displayed 3 Select the language you require The displa...

Страница 64: ...ransmission devices are activated To end activation of the selected elements 1 In the start menu select Maintenance 2 Activate transmission device 3 Select the list fields of the activated transmission devices 4 Select Off The transmission devices are no longer activated 14 5 Bypassing Un bypassing buzzer In order to prevent an acoustic warning tone being sent to the panel during maintenance work ...

Страница 65: ...ifferent signal tone to the one it emits in the alarm state 15 1 Walktest groups The following options are available for switching elements to walktest Select individual elements from lists and or Select previously defined walktest groups consisting of at least one element There are 12 pre defined walktest groups The number of possible walktest groups is predefined January to December Example Dete...

Страница 66: ...w elements Only those elements which have not been assigned to any walktest group yet will be displayed Various element categories are displayed 1 Select the category you require A list of elements is displayed See also Working with lists page 24 2 Select an element The element is marked 3 Select Add The selected element is added to the group Delete Old Select this function field to delete one or ...

Страница 67: ... the elements for the walktest and to switch them to walktest 1 In the start menu select Maintenance 2 Walktest 3 Start End walktest Various element categories are displayed 4 Select More to display further categories or one of the displayed categories or Select by number and enter the number of the element into the search screen see also Search Function Element page 26 Notice If you select the el...

Страница 68: ...hat showed no reaction during the test or that have not been tested Select Tested to display the elements that were tested and showed a reaction 15 5 Assigning tested elements to a walktest group Notice Only those elements in the current walktest that have been tested can be assigned to a different walktest group On completion of the walktest you can assign the tested elements to a different walkt...

Страница 69: ...Starting date end date and time Event types Message types such as Fault Device types Device types such as Detectors Address range Address range within a system User commands Selected function fields such as Acknowledge or Reset Walktest Elements switched to walktest mode If one or more filters have been set the Change filter field in the status bar is highlighted in a dark color 16 2 Setting filte...

Страница 70: ... The following functions are offered To switch to the status bar on the start page press the double arrow key in the status bar or on the membrane keypad Change filter If the field has a black background a filter has been set Select this field to set a different filter Go to no Enter the number of a specific event The event with the selected number is displayed at the start of the list Go to day E...

Страница 71: ...rting from latest event For the printout enter a particular number of events counted from the most recent event Event numbers to be printed To print out a particular range specify by entering event numbers A checkmark is placed in the selection field 4 Enter the numbers you require 5 Select OK to confirm the entry A list of the printers that can be selected is displayed 6 Select a printer 7 Select...

Страница 72: ...n panels in night mode if at least one panel in the network is in day mode Standalone Network Night mode Panel is in night mode All networked panels in the network scope are in night mode Day mode Panel is in day mode Night day combination Panel is in night mode but at least one other panel in the network scope is in daymode Notice Please note that following a transmission fault it may be necessar...

Страница 73: ...panel that are currently switched to day mode To display a list of all detector groups in day mode 1 In the start menu select Switch to day mode or Switch to night mode depending on which mode the panel is currently in or select the day mode or night mode icon on the status bar 2 Select Show details A list of all logical zones that are switched to day mode is displayed 17 3 Changing the time for r...

Страница 74: ...nter the numbers you require Select OK to confirm the entry or Cancel to cancel the operation The entries are confirmed To change the set back time in day mode to night mode 1 On the status bar select 2 or In the start menu select Switch to night mode 3 Select Change time 4 Enter the numbers you require Select OK to confirm the entry or Cancel to cancel the operation ...

Страница 75: ...N a reboot of the panel is required To change the physical node address enter a number between 1 and 64 Choose OK and reboot to make the change effective 18 3 Group setting Different kind of groups can be created using the FSP 5000 RPS programming software Bypass isolate and walktest groups and input output groups Each group can consist of one or more element s Input groups consist of several dete...

Страница 76: ...w Select this function field to add one or more new elements Only those elements that have not yet been assigned to an input group will be displayed Various element categories are displayed 1 Select the category you require A list of elements is displayed 2 Select an element The element is marked 3 Select Add The selected element is added to the group Delete Old Select this function field to delet...

Страница 77: ...he detector or logical zone lists that are offered A list of elements is displayed Depending on the list you have selected enter the number or the name of the element into the search screen 3 Select the list field you require e g a logical zone in this case Two settings are displayed There is a checkmark in the selection field in front of the active setting 4 Select the selection field of the dete...

Страница 78: ...he access level for which the password is to be changed select the list field you require 5 Enter a new password and repeat the entry in the bottom field again On the display each digit of the password is indicated with an asterisk so that nobody else can see the password 6 Select OK to confirm the entry or Cancel to cancel the operation The entry is confirmed 18 5 3 Set Default Password 1 In the ...

Страница 79: ...he secure network gateway for Remote Services with the panel and the internet access point 2 Go to Configuration Network services Ethernet IP settings Enter the IP address of the panel Check the Use Ethernet settings box For details please see IP settings page 30 3 Restart the panel by removing the power supply or using the reset button 4 Go to Configuration Network services Change date time Enter...

Страница 80: ...00 FPA 1200 AVENAR panel 8000 AVENAR panel 2000 AVENAR keypad 8000 2020 07 3 0 F 01U 378 877 User Guide Bosch Sicherheitssysteme GmbH Configuration version Config version Number Name IP address Scope Country Time zone Menu name ...

Страница 81: ...an be operated and passwords and names can be changed One of the following two options is offered Entering a master password that is valid indefinitely This password cannot be changed and is available from the relevant Bosch branch on request Entering a master password that is valid for a specified period of time This password is only valid for 24 hours The panel controller can issue a number on r...

Страница 82: ...emote connection is still active Teleservice Active is displayed To blank out the text touch the screen The text re appears every 30 seconds for as long as the remote connection remains active To create a remote connection via telephone In the start menu select Further functions Remote access Enable call The system can now be called from remote Afterwards the connection is disconnected Active is d...

Страница 83: ...e can see the password 5 Enter a new password and repeat the entry in the bottom field again 6 Select OK to confirm the entry or Cancel to cancel the operation 19 6 Performing a fire drill During a drill all signaling devices are activated Caution If a genuine alarm is reported during a fire drill the fire drill is abandoned The fire drill can only be restarted when the alarm is ended To start a d...

Страница 84: ...rm conditions and messages which have been counted so far 1 In the start menu select Further functions 2 Alarm counters The figure after the message type shows the number of conditions and messages counted so far for the individual panel Local and summed up for all panels in the complete network or a network group depending on the configuration Scope Notice The scope of the counters depends on the...

Страница 85: ...nction 20 1 Menu overview Reset Event type Scope Logical zone Detector This panel 20 2 Resetting elements To reset a detector or logical zone for example 1 In the start menu select Reset 2 Select the element you require 3 Select the detector or zone 4 Select the required list fields The list fields are marked A list of the detectors or zones is displayed 5 Select Reset The selected elements are re...

Страница 86: ...nt immediately Press All On to activate all elements or All Off to stop the activation of all elements at a time Use and to scroll through the list The element entries change their background color according to their current state The background colors of the elements have the following meaning Red Elements which are actively being controlled in case of an alarm Fuchsia Elements which are actively...

Страница 87: ...000 AVENAR keypad 8000 Control Monitor en 87 Bosch Sicherheitssysteme GmbH User Guide 2020 07 3 0 F 01U 378 877 2 Search function A list of all functions is displayed 3 Select the list field you require The submenu of the selected function is displayed ...

Страница 88: ... configuration Reset to Factory Settings This function is currently not implemented Calibrate Touchscreen To calibrate the touchscreen press the button and follow the instructions on the screen If the touchscreen is totally decalibrated and touching the button does not work touch the screen at any position for at least 4 seconds and then release Releasing also starts the calibration process Update...

Страница 89: ...anging language display 10 28 63 Changing time for resetting to night mode 73 Checking access authorization 23 Configuration version 80 Consistency check 59 Country 80 D Day mode 36 72 Day night mode showing details 73 Day night mode switching 72 Default language 63 Deleting numbers 28 Description search by 26 Detector sensitivity 77 Diagnostics 56 Diagnostics All info for one element 56 Diagnosti...

Страница 90: ...sion Level 58 Performing a fire drill 83 Physical addressing 29 Physical node address RSN 75 Physical node number 59 Ping command 60 Power button 20 Production Date 58 Q Quick entry of text and numbers 28 R Remote keypad display 32 Remote keypad operation 32 Remote Maintenance State of Remote Maintenance 60 Rename elements 78 Reset counters 84 Resetting alarm message 43 Resetting external signalin...

Страница 91: ...m manually 43 Triggering fire verification 42 Types of alarm 34 U Unblocking elements 54 Un bypassing bypassed element groups 50 Un bypassing elements 50 V Voice Alarm System Plena 61 VAS over IP 61 W Walktest Group 76 Walktest groups 65 Walktest groups adding elements 65 Walktest groups deleting elements 65 Walktest displaying tested elements 68 Walktest displaying untested elements 68 Water 34 ...

Страница 92: ...92 Index FPA 5000 FPA 1200 AVENAR panel 8000 AVENAR panel 2000 AVENAR keypad 8000 2020 07 3 0 F 01U 378 877 User Guide Bosch Sicherheitssysteme GmbH ...

Страница 93: ......