16
UPS, please refer to the layout diagram.
2) For the B500EVO-100-B UPS, it is recommended to select the
UL1015 8AWG(10mm
2
) wire or other insulated wire which
complies with AWG Standard for the UPS input and output
wirings.
3) For the B500EVO-200-B UPS, it is recommended to select the
UL1015 6AWG(25mm
2
) wire or other insulated wire which
complies with AWG Standard for the UPS input and output
wirings.
Note:
Do not use a wall receptacle as the input power source
for the UPS, if its rated current is less than the UPSs
maximum input current. This can result in serious
damage.
5) Connect the input and output wires to the corresponding input
and output terminals according to the connection diagram.
Note:
you must make sure that the input and output wires and
the input and output terminals are connected tightly.
6) The protective earth wire refers to the wire connection
between the equipment which consumes electric equipment
and the ground wire. The diameter of the protective earth
should be at least the minimum requirement for each model
and only appropriate wire should be used.
7) After having completed the installation, make sure the wiring is
correct.
8) An output breaker must be installed between the output
terminal and the load, this breaker should work based on
leakage current.
9) To connect the load to the UPS, turn off all the loads first, then
make the connection and finally turn on the loads one by one.