37
UPS which is currently operated in a parallel redundancy
system. All other UPSs continue working to supply the load in
the parallel system.
2) The “Single UPS battery test” command is designed to control
one UPS which is currently operated in a parallel system for
single battery testing. The other UPSs do not do the battery
test.
3) The “Parallel UPS battery test” is designed to control all UPS in
a parallel system to do the battery test at the same time.
4) “Clear EPO status” once EPO status is enabled, the UPS
output will be cut off. To recover to normal status, first the EPO
connector should be closed, and enter this menu to clear EPO
status, then the UPS will stop the alarm and recover to Bypass
mode. The UPS should be turned on by manual operation.
5) “Reset Fault status” when a fault occurs, the UPS remains in
Fault mode and alarms. To recover to normal status, enter this
menu to reset error status, then the UPS will stop the alarm and
recover to Bypass mode. The cause of the fault should be
checked and dealt with before the UPS is turned on again by
manual operation.
6) Restore factory settings: all the settings can be recovered to
default factory settings. This can only be done in Bypass mode.