will transfer to Battery mode and the load is supplied continuously.
The main advantage of this mode is the output frequency is fixed. This
can be required for some particularly sensitive loads.
This additional protection means that the load capacity of the UPS
should be reduced to 60% when used in converter mode.
6.2.2 Set the function
This function could be enabled through the LCD setting in Bypass
mode.
Enter the power strategy setting menu by following chapter of 5.5.7.
6.3 Parallel function
6.3.1 Brief introduction of the redundancy
N+X is currently the most reliable power supply structure. N represents
the minimum UPS number that the total load needs, X represents the
redundant UPS number, i.e. the fault UPS number that the system can
handle simultaneously. When the X is larger, the reliability of the power
system is higher. For occasions where reliability is highly depended on,
N+X is the optimal mode.
As long as the UPS is equipped with parallel cables, up to 4 UPSs can
be connected in parallel to realize output power sharing and power
redundancy.