EN
15
Installation
www.bora.com
min. 700*
min. 74
176
900
(min.
890)
**
120
252
285
min.
100
170
682
max. 562
max. 430
389*
110
PKA3 mit Flachschalldämpfer USDF, Flachkanalverbinder
EFV und Übergangsstück Versatz EFRV110 (Zeile):
PKA3 mit Rundschalldämpfer USDR50 und Rundkanal-
verbinder ERV (Insel):
PKAS3 mit Ecotube Flachkanal:
PKA3 mit Flachschalldämpfer USDF, Flachkanalverbinder
EFV und Übergangsstück gerade EFRG (Insel):
min. 700
min. 74
199
min.
100
120
691
min. 455
58
min. 328
max. 580
592
152
min. 810*
min. 74
176
900
(min.
890)
**
220
min.
100
110
760
max. 545
219*
151*
BORA Professional 3.0
B O R A L Ü F T U N G S F I B E L
XX
min. 810*
min. 74
176
900
(min.
890)
**
120
min.
100
93
min. 742
max. 562
219*
151*
295
33
180
810
Fig. 5.3
Appliance installation dimensions for standard set-up
of PKA3/PKA3AB with round silencer USDR50
5.4.3 Worktop and kitchen units
X
X
Create the worktop cut-out taking into account the specified
cut-out dimensions.
X
X
Make sure that the cut surfaces of the worktops are properly
sealed.
X
X
Comply with the instructions of the worktop manufacturer.
X
O
Cross bars on the kitchen unit in the area of the worktop cut-
out may need to be removed.
X
O
No false floor is necessary below the cooktop. If cable
protection (false floor) is planned, the following must be taken
into account:
X
O
it must be fitted in such a way that it can be removed for
maintenance work;
X
O
to ensure sufficient cooktop ventilation, a minimum
distance of 15 mm to the bottom edge of the cooktop is
to be observed.
X
O
The drawers and/or shelves in the floor unit must be
removable.
X
O
For correct installation, the drawers of the floor unit must be
shortened depending on the installation situation.
5.4 Assembly instructions
5.4.1 Safety clearances
X
X
Maintain the following safety clearances:
1
3
2
Fig. 5.1
Minimum distance
[1]
Minimum clearance of 50 mm at the back from the worktop
cut-out to the rear edge of the worktop (in the case of
cooktops PKC3, PKCB3 and PKCH3 the minimum clearance is
70 mm when the cooktop is installed rotated by 180°).
[2]
Minimum clearance of 300 mm from the left and right of the
worktop cut-out to the adjacent cabinet or wall.
[3]
Minimum clearance of 600 mm between the worktop and the
wall unit.
5.4.2 Minimum installation dimensions
(standard set-up)
≥810
≥890
≥900
Fig. 5.2
Minimum installation dimensions for standard set-up
of PKA3/PKA3AB
Содержание PKCH3
Страница 33: ...EN 33 Notes www bora com 11 Notes...
Страница 34: ...EN 34 Notes www bora com...
Страница 35: ...EN 35 Notes www bora com...