User’s Manual
33
4.4.
F
AULTS
The M3645 monitors a number of different fault conditions which prevent the regen
from operating. Some faults latch until they are reset by toggling the enable input.
Faults that do not latch will automatically clear when the fault condition is no longer
present. Every fault opens the Ready output contact (4.5.5).
On units with a digital display, the display stores the last 50 fault records (4.3.5). On
units without a digital display only the most recent fault state can be viewed. T
he unit’s
most recent fault state may be accessed by disabling the unit (4.5.2), then setting the
Fault Recall Input (4.5.3) high. The red Not Ready LED (4.2.2.3) will blink out all the
faults of the most recent fault state, in sequence.
Table 4-1: Blink Codes
F
LASHES
F
AULT
Solid
Unit is not Enabled
1 Fast
Feedback Undervoltage
2 Fast
Overtemperature
3 Fast
DC Overvoltage
4 Fast
Differential Overvoltage
5 Fast
Sync Loss
1 Slow
IGBT Driver
2 Slow
Phase Overcurrent
3 Slow
Phase Loss
4 Slow
DC Undervoltage
5 Slow
Regen Power-On/Precharge Not Complete
6 Slow
Frequency Detect Failure
Note: Slow: 1 blink per second
Fast: 3 blinks per second
4.4.1.
F
EEDBACK
U
NDERVOLTAGE
This fault indicates that the M3645's DC bus feedback circuitry has failed.
This fault will latch until manually cleared by toggling the Enable Input. If this
fault does not clear, it typically indicates that damage to the M3645 has
occurred and must be repaired.
4.4.2.
O
VERTEMPERATURE
This fault indicates that the regen unit has exceeded its safe operating
temperature. This fault will automatically clear when the unit's temperature
has returned to a safe level.
4.4.3.
DC
O
VERVOLTAGE
This fault indicates that the DC voltage on the bus has exceeded 1000V. This
fault latches until manually cleared.
4.4.4.
D
IFFERENTIAL
O
VERVOLTAGE
This fault indicates that the DC bus is more than 200V higher than the AC
line peak. This fault latches until manually cleared by toggling the Enable
input.
Содержание M3645
Страница 14: ...M3645 14 This page intentionally left blank ...
Страница 22: ...M3645 22 Figure 3 5 300A Connection Locations ...
Страница 27: ...User s Manual 27 Figure 3 10 M3645 300A Regen Customer Power Wiring ...
Страница 30: ...M3645 30 This page intentionally left blank ...
Страница 44: ...M3645 44 6 6 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3645 M10 Chassis Dimensional Outline ...
Страница 45: ...User s Manual 45 Figure 6 2 M3645 M11 Chassis Dimensional Outline ...
Страница 46: ...M3645 46 Figure 6 3 M3645 M12 Chassis Dimensional Outline ...
Страница 47: ...User s Manual 47 Figure 6 4 M3645 M15 Dimensional Outline ...
Страница 48: ...M3645 48 Figure 6 5 M645 x300R Line Reactor Dimensional Outline ...
Страница 50: ...M3645 50 6 7 BLOCK DIAGRAM Figure 6 7 M3645 30A 50A 100A Functional Block Diagram ...
Страница 53: ...User s Manual 53 NOTES ...
Страница 54: ...M3645 54 ...
Страница 55: ......