The diagrams shown in Figures 3-9, 3-10, 3-11 illustrate typical connections of the
M3645 regen units with generic VFDs. There are many other configurations that may
be applied providing a basic connection criterion is maintained such as:
The AC input should maintain a low impedance path back to the grid.
No reactors should be connected upstream of the regen unit without consulting
Bonitron for instructions.
The DC input should be connected to a fixed bus whether from a common bus
supply or from the output of a VFD. This should never be connected to a switching
source such as the braking resistor terminals on some drives.
The DC input should not be connected to an active front end drive without
instructions from Bonitron.
Содержание M3645
Страница 14: ...M3645 14 This page intentionally left blank ...
Страница 22: ...M3645 22 Figure 3 5 300A Connection Locations ...
Страница 27: ...User s Manual 27 Figure 3 10 M3645 300A Regen Customer Power Wiring ...
Страница 30: ...M3645 30 This page intentionally left blank ...
Страница 44: ...M3645 44 6 6 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3645 M10 Chassis Dimensional Outline ...
Страница 45: ...User s Manual 45 Figure 6 2 M3645 M11 Chassis Dimensional Outline ...
Страница 46: ...M3645 46 Figure 6 3 M3645 M12 Chassis Dimensional Outline ...
Страница 47: ...User s Manual 47 Figure 6 4 M3645 M15 Dimensional Outline ...
Страница 48: ...M3645 48 Figure 6 5 M645 x300R Line Reactor Dimensional Outline ...
Страница 50: ...M3645 50 6 7 BLOCK DIAGRAM Figure 6 7 M3645 30A 50A 100A Functional Block Diagram ...
Страница 53: ...User s Manual 53 NOTES ...
Страница 54: ...M3645 54 ...
Страница 55: ......