Modbus Agile
02/2011
16
RS485 and RS232 Interfaces
5.2.2
Pin Assignment
5.2.2.1
RS232 Communication Module CM-232 DB9
X310
The RS232-Interface is connected to a PC or a controller via
the 9-pin D-Sub socket X310.
The assignment complies with the standard, so that only an
RS232 connection cable (1:1) is required.
Bus Connector X310 CM-232 (9-pin D-Sub)
Pin
Name
Function
Housing
Shield
connected with PE
1
–
n. c.
2
RxD
receive data
(input)
3
TxD
transmit data (output)
4
–
n. c.
5
0 V
Ground
6
–
n. c.
7
–
n. c.
8
–
n. c.
9
–
n. c.
n.c: not connected
5.2.2.2
RS485 Communication Module CM-485 DB9
S1
X310
ON
The RS232-Interface is connected to a PC or a controller
via the 9-pin D-Sub socket X310.
For details on the pin assignment, refer to the following
table.
Bus Connector X310 CM-485 (9-pin D-Sub)
Pin
Name
Function
Housing
Shield
connected with PE
1
Data Line B
short-circuit proof and functionally insulated; max. current 60 mA
2
Data Line B’
same as pin 1 – for cable network
3
0 V
GND/earth
4
–
n. c.
5
+5 V
Interface converter supply v5 V
6
–
n. c.
7
Data Line A
short-circuit proof and functionally insulated; max. current 60 mA
8
Data Line A’
same as pin 7 – for cable network
9
–
n. c.
n.c: not connected
Содержание Agile
Страница 1: ...Agile Modbus Communication manual Frequency inverter 230V 400V ...
Страница 2: ......
Страница 5: ...Modbus Agile 5 02 2011 13 2 Warning Messages Application 76 13 3 Error Messages 76 INDEX 77 ...
Страница 44: ...Modbus Agile 02 2011 44 Handling of Data Sets Cyclic Writing ...
Страница 69: ...Modbus Agile 69 02 2011 10 2 1 Statemachine diagram ...
Страница 78: ......
Страница 79: ......