Modbus Agile
17
02/2011
RS485 and RS232 Interfaces
5.2.2
Pin Assignment
5.2.2.1
RS232 Communication Module CM-232 DB9
X310
The RS232-Interface is connected to a PC or a controller via
the 9-pin D-Sub socket X310.
The assignment complies with the standard, so that only an
RS232 connection cable (1:1) is required.
Bus Connector X310 CM-232 (9-pin D-Sub)
Pin
Name
Function
Housing
Shield
connected with PE
1
–
n. c.
2
RxD
receive data
(input)
3
TxD
transmit data (output)
4
–
n. c.
5
0 V
Ground
6
–
n. c.
7
–
n. c.
8
–
n. c.
9
–
n. c.
n.c: not connected
5.2.2.2
RS485 Communication Module CM-485 DB9
S1
X310
ON
The RS232-Interface is connected to a PC or a controller
via the 9-pin D-Sub socket X310.
For details on the pin assignment, refer to the following
table.
Bus Connector X310 CM-485 (9-pin D-Sub)
Pin
Name
Function
Housing
Shield
connected with PE
1
Data Line B
short-circuit proof and functionally insulated; max. current 60 mA
2
Data Line B’
same as pin 1 – for cable network
3
0 V
GND/earth
4
–
n. c.
5
+5 V
Interface converter supply v5 V
6
–
n. c.
7
Data Line A
short-circuit proof and functionally insulated; max. current 60 mA
8
Data Line A’
same as pin 7 – for cable network
9
–
n. c.
n.c: not connected
5.2.2.3
RS485 Communication Module CM-485T
The RS485-Interface is connected via the 7-pin terminal
socket X310.
For details on the pin assignment, refer to the following
table.
Bus Connector X310 CM-485 T (7-pin terminal socket)
Terminal
Name
Function
1
Data Line A
short-circuit proof and functionally insulated; max. current 60 mA
2
Data Line A’
same as pin 1 – for cable network
3
Data Line B
short-circuit proof and functionally insulated; max. current 60 mA
4
Date Line B’
same as pin 3 – for cable network
5
+5 V
Interface converter supply v5 V
6
0 V
GND/earth
7
PE
Shield
5.2.3
RS485 Bus Termination
Attention!
The passive bus termination (connection of a termination resistor), is required at the physically first
and last client. It can be activated by the CM-485 and CM-485T DIP Switch S1.
By default, the bus termination is set to OFF.
It is important to implement a correct termination. Otherwise, no communication is possible via the
RS485-Interface.
As an alternative, the active bus termination is possible via a corresponding circuit:
The active termination is only allowed once on each branch. The bus termination via an external cir-
cuit and via DIP switch at the same time is not allowed.
Pay attention to the ground wiring. This will protect the communication bus against high noise level.
For easy wiring the signal terminals A and B have parallel contacts.
Pin 5 +5 V
330
Ω
Pin 3 0 V
GND
150
Ω
22.1
Ω
330
Ω
Data line A
Pin 7
Pin 8
22.1
Ω
Data line B
Pin 1
Pin 2
Содержание Agile
Страница 1: ...Agile Modbus Communication manual Frequency inverter 230V 400V ...
Страница 2: ......
Страница 5: ...Modbus Agile 5 02 2011 13 2 Warning Messages Application 76 13 3 Error Messages 76 INDEX 77 ...
Страница 44: ...Modbus Agile 02 2011 44 Handling of Data Sets Cyclic Writing ...
Страница 69: ...Modbus Agile 69 02 2011 10 2 1 Statemachine diagram ...
Страница 78: ......
Страница 79: ......