Modbus Agile
65
02/2011
Control / Reference Value
10.1 Control via Contacts / Remote-Contacts
In the operation mode "Control via Contacts" (
Local/Remote
412 = 0), the frequency inverter is con-
trolled via the digital inputs or via the multi-functional inputs that have been set to digital inputs.
In the operation mode "Control via Remote Contacts" (Parameter
Local/Remote
412 = 2), the fre-
quency inverter is controlled via the individual bits of the virtual digital inputs in the Control Word.
If the frequency inverter is controlled via the digital inputs, then in this operation mode control via the
Control Word 410 does not apply.
Control Word (
Local/Remote
412 = 2)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
STOA und STOB
1
IN1D
2
IN2D
3
IN3D
4
IN4D
5
IN5D
6
MFI1D
7
MFI2D
8
-
9
-
10
-
11
-
12
-
13
-
14
-
15
-
If the operation mode "Control via Remote Contacts" is used, then the Controller Release
"STOA+STOB" must be switched on and bit 0 of the Control Word must be set, in order to start the
drive.
With the use of Remote Contacts the signal sources (digital inputs or multifunctional inputs set as
digital inputs) are taken virtually from the
Control Word
410. Signals at the hardware terminals are
not evaluated in the standard operation modes (e.g. 72 - IN2D).
Operation modes which are marked with the extension "(Hardware") are available in order to evaluate
signals at the hardware terminals.
Exceptions: The release must always be made via the Hardware-Inputs STOA (Terminal X11.3) and
STOB (Terminal X13.3) and bit 0 "STOA+STOB" of the Control Word.
A Controller Release by software alone is not possible.
Parameter
Status Word
411 has a length of 16 bits. The set bits have the following meaning:
Status Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
Ready to Switch On
1
Switched On
2
Operation enabled
3
Error
4
Voltage enabled
5
Quick Stop
6
Switch On disabled
7
Warning
8
-
9
Remote
10
Reference value reached
11
Limit value reached
12
-
13
-
14
-
15
Warning 2
Note:
The frequency inverter supports an external 24 V voltage supply for the control electronics of the fre-
quency inverter. Communication between the controlling device (PLC) and the frequency inverter is
still possible even when the mains supply has been switched off.
Bit 4 "Voltage enabled" in the Status Word indicates the current status of the mains supply.
Bit 4 "Voltage enabled" = 0 signals "no mains supply" and that starting the drive is not possible.
Bit 4 "Voltage enabled" = 1 signals "mains supply switched on" and drive ready for starting.
Содержание Agile
Страница 1: ...Agile Modbus Communication manual Frequency inverter 230V 400V ...
Страница 2: ......
Страница 5: ...Modbus Agile 5 02 2011 13 2 Warning Messages Application 76 13 3 Error Messages 76 INDEX 77 ...
Страница 44: ...Modbus Agile 02 2011 44 Handling of Data Sets Cyclic Writing ...
Страница 69: ...Modbus Agile 69 02 2011 10 2 1 Statemachine diagram ...
Страница 78: ......
Страница 79: ......