Table 1.4.2.1
Input Configuration Parameters (Input Attributes)
Activation Delay for
Output 1
Output activation (deactivation) delay from
moment of an input status change
0 to 255 s
Activation Delay for
Output 2
Activation Delay for
Output 3
Activation Delay for
Output 4
Activation Delay for
Output 5
Activation Delay for
Output 6
Activation Delay for
Output 7
Parameter
Function
Acceptable values range
1
2
3
Input Type
Defines the tactics of input monitoring, class of
connected detectors and possible input states
1 – Smoke Fire (two-threshold)
2 – Combined Fire (one- threshold)
3 – Heat Fire
(two-threshold)
4 – Intrusion
5 – Intrusion and Fire
6 – Auxiliary
7 – Lobby
11 – Panic
12 –
Programmable Auxiliary
16 – Fire Manual
17 – Flood Alarm
18 – Manual Release
Zone Number
The zone number that includes this fire input (only
for Input Type 1, 2 and 3)
0 to 10
(0 is not included in any zone)
Alarm Delay
Transition delay from Lobby Alarm to Intrusion
Alarm status for Intrusion Input (type 7) and
Transition delay to Flooding Detected status for
Flood Alarm Input
0 to 255 s
Arming Delay
Pause between input arming command and input
transition to Armed status
0 to 255 s
Delay Analysis after Reset
Time required for power restore process after reset
within input
The input is not analyzed during this time
1 s 63 s
Shunt Time
Time required for input restoring from Intrusion
Alarm, Panic and Armed states.
For Auxiliary Input: this is a transition time to
Armed, Disarmed and Auxiliary Normal and any
…. Restored
Flood Alarm Input: this is a transition time to
Flood Alarm Restored state.
0 to 255 s