72
When the specified menu item is selected, indicator “13” turns on steady red, and the “Access”
indicator turns off.
To change the network address, the following shall be done must:
- enter a new network address (available values 1 ... 127) using buttons ‘1’ ... ‘10’ (button ‘10’
corresponds to number ‘0’);
- press the Enter button.
To cancel network address changes and to return the device to Quiescent mode, press the
button .
When trying to change the network address, errors may occur. Description of errors is provided in
Table 1.4.4.16
Table 1.4.4.16
Network Address Change Errors
Description
Error Code
(Indicator No)
Invalid address is entered (beyond the range 1…127)
1
Error saving address
2
If an error occurs while changing a network address, indicator ‘13’ is off.
The panel displays an error code for 3 seconds by turning a corresponding indicator intermittent
red. For example, if the error code is 1, the indicator ‘1’ will be turned red in the intermittent mode for 3
seconds
The display of the error code is accompanied by a long beep.
After successful deleting all credentials or error code indication, the panel returns to the Installer
Menu.
If, within 20 seconds after selecting a menu item, the Enter button is not pressed twice, the panel
returns to the Quiescent mode.
Return to the Quiescent mode is accompanied by a short triple beep.
1.4.5.74
The Diagnostics
: Output control
item allows manually enabling/disabling the panel
outputs regardless of the control mode (local or centralized).
Warning!
Please, disconnect all actuating circuits from outputs, which shall not be
activated during test procedure!
When this menu item is selected, indicator “14” turns steady red and the Access indicator is off.
The outputs are controlled using the corresponding buttons “1” …”7”. Each pressing changes the
corresponding output state.
Activation of non-monitored outputs “1” ... “3” is indicated red by corresponding indicators “1 …
3”).
The current state of the monitored outputs (on / off; normal / open / short circuit) is displayed on
the corresponding indicators (‘OUTPUTS: 4 ... 7’). The indication is described Table 1.4.4.16.1.