57
1.4.5.42
When the Touch Memory credential is presented to the reader (or password is entered),
the panel transmits the credential code to the network controller and waits a response about the control
rights to this credential.
At this moment, the ‘Access’ indicator switches from red to green with a frequency of 4 Hz.
The process of waiting for a response can take from fractions of a second to several seconds,
depending on the number of devices in the RS-485 interface
1.4.5.43
If the presented credential has no rights, the control panel indicates a Deny in access to
control (long acknowledging sound signal and intermittent switching on of the Access indicator in red for
3 seconds) and returns to the Quiescent mode.
1.4.5.44
If the presented identifier has rights to control the partition, the panel will display the
status of this partition on the ‘Access’ indicator, in accordance with
1.4.5.45
Each repeated presentation of the Touch Memory credential (or pressing the Enter
button), if the credential has the rights to “
Arming
” and “
Disarming
” the partition, will cause:
–
an attempt to arm the partition (if the partition was disarmed);
–
disarming the partition (if it was in other states).
If the credential has limited rights to control the partition, for example, only arming is allowed, the
repeated presentation (as well as all subsequent ones) of this credential causes only the permitted action
(arming), regardless of the current state of the partition.
1.4.5.46
In the Centralized Control mode, the panel interacts with the network controller in the
same manner as in the
Quiescent
mode.
1.4.5.47
Switching to the
Quiescent
mode from the
Centralized Control
mode is performed by
the following way:
–
Manually using the
_____
button
–
Automatically after 20 seconds after the last action (button presenting or credential
presenting).
1.4.5.48
The panel can go to the Administrator menu in the following manners:
–
from the PIN Entry mode, after entering the Administrator PIN code;
–
from the ‘Quiescent or PIN Entry, after presenting an administrator credential to the reader.
1.4.5.49
Switching to the Administrator Menu is accompanied by the following:
–
Administrator melody;
–
Turing off all indication;
–
cyclical alternating turning on indicators ‘11’ ... ‘20’ in green (‘running green line’).
1.4.5.50
The Administrator can press the corresponding button to select menu items specified in
Table 1.4.4.2.
Table 1.4.4.2
Administrator Menu
Menu Item
Button
Add New Credential
Edit Credential Rights
Edit Credential Rights by Number
Change User Credential
Change User Credential by Number
11
12
13
14
15