9
Current conditions
LED Indicators
Buzzer
POWER BATERY FAULT
RS-485
12 V
green
green
amber
green
green
7. Mains voltage failed; batteries voltage
is lower than 10.2 V (during first two
hours)
─
+
/
─
1 Hz
─
+
1
─
+
8. Mains power failed; battery voltage is
lower than 10.2V (after two hours)
─
─
ON
10 s
─
─
ON
10 s
9. Mains voltage is lower than 150 V or
higher than 260 V
+
/
─
1 Hz
+
─
+
1
+
ON
0.8 s
10. Batteries are in poor condition
(replacement required)
+
+
/
─
1 Hz
+
/
─
1 Hz
+
1
+
5 beeps
11. Charger failure
+
+
/
─
4 Hz
+
/
─
4 Hz
+
1
+
ON
0.8 s
12. ShPS-12’s output overvoltage
+
/
─
1 Hz
+
/
─
1 Hz
+
/
─
1 Hz
+/
─
1 Hz
─
─
1
When communications over RS-485 is in the normal condition. If communications fails, it is
turned off. If initially normal communications over RS-485 fail, the RS-485 LED starts 1-Hz
flashing after 30 seconds of failure occurrence.
h)
The ShPS-12 can transmit the following messages over RS-485:
−
Device Reboot (when the ShPS-12 has been powered on);
−
Mains Failed (the mains supply voltage is lower than 150 V or higher 250 V);
−
Mains Restored (the mains supply voltage recovered to the range of 150V to 250V );
−
Overload (the ShPS-12’s output current exceeds 3.5 A);
−
Load Restored (the ShPS-12’s output current has been normal (less than 3.5 A));
−
Charger Failed (the charger failed to provide proper voltage and current to charge the batteries);
−
Charger Restored (charger provides proper voltage and current values to charge the batteries);
−
Power Failed (the mains power being applied to the box, the ShPS-12 does not provide functions
according to 1.2.4);
−
Power Restored (the mains power being applied to the box, the ShPS-12 provides functions
according to 1.2.4);
−
Battery Fault (voltage of any of the batteries is lower than 7V or batteries are not connected);
−
Battery Test Error (battery internal resistance is higher than a critical threshold, and the batteries
have to be replaced or maintained, see item 10 in Table 3);
−
Battery Low (battery voltage is lower than 11 V, mains power being not available);
−
Service Required (battery lifetime has expired; the batteries are subject to replacement);
−
Battery Restored (voltage produced by batteries exceeds 10V; the batteries can be charged);
−
Tamper Alarm (the ShPS-12 enclosure has been opened);
−
Tamper Restored (the ShPS-12 enclosure has been closed);
−
Output Voltage Off (the ShPS-12 has turned off the output voltage due to the mains failed and
batteries discharged);
−
Output Voltage On (the ShPS-12 has turned on the output voltage upon the mains power is
restored after batteries discharging).
If in the moment of message generation there is no connection with a network controller over RS-
485, the message is stored in non-volatile memory of ShPS-12, and it will be transmitted as soon as the
connection is recovered. The time stamp of message will get the actual time of the event occurrence.
The buffer (event log) in the nonvolatile memory of the ShPS-12 can store up to 95 events.
Содержание ShPS-12
Страница 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Страница 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Страница 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Страница 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...