6
No.
Parameter
Value
1.2.18.
Time to charge fully discharged batteries
Maximum charging rate for each battery
36 hours max
0.7 A
1.2.19.
Maximum current available for additional consumers of mains power
220V / 50Hz
10 A
1.2.20.
Electric shock protection class as per GOST 12.2.007.0-75
I
1.2.21.
Enclosure protection degree as per GOST 14254-2015
•
ShPS-12, ShPS-12 mod.01, ShPS-12 mod.10, ShPS-12 mod.11
•
ShPS-12 mod.02, ShPS-12 mod.12
IP41
IP54
1.2.22.
Resistance to mechanical exposure as per OST 25 1099-83
Arrangement Category III
1.2.23.
Vibration exposure:
- Frequency range
- Max acceleration
1-35 Hz
0.5 g
1.2.24.
Environmental category as per OST 25 1099-83
О
3
1.2.25.
Operating temperature range
Minus 10 t40 °
С
1.2.26.
ShPS-12 weight without batteries / with batteries
15 / 27 kg
1.2.27.
Overall dimensions
650
×
500
×
220 mm
1.2.28.
Non-stop operation
Round-the-clock
1.2.29.
MTBF
40000 h
1.2.30.
Survival probability over a period of 1000 hours
0.975
1.2.31.
Expected service life of ShPS-12
10 years
* The letters
С
and
М
define the battery service life as 12 and 15 years respectively.
** The maximum load current is 3.5 A (for short-duration periods of up to 2 minutes at intervals
of at least one hour provided that the mains power is available and batteries are connected). When the
output current exceeds 3.5 A, the ShPS-12 box turns off the charger. When the output current is over
4A, ShPS-12 disables the output voltage.
1.2.32.
ShPS-12 provide monitoring mains voltage, output voltage, and battery voltage with automatic
sending over the RS-485 interface messages about presence of relevant voltages / faults, battery dis-
charge, bad battery health and battery disablement, and tampering.
1.2.33.
The built-in PSU of ShSP-12 is ready to operate after 6 seconds upon powering up.
1.2.34.
A ShPS-12 features a Remote Fault Output – a solid state relay with the following parameters:
maximum switched voltage / current is 80 V / 50 mA; maximum resistance of closed relay circuit is
50 Ohm; maximum open circuit leakage current at 80 V is
1
uA.
1.2.35.
ShPS-12 support event sharing over RS-485 (see 1.4.2-h) and executing commands instructed
over RS-485.
1.2.36.
ShPS-12 boxes provide programming parameters in their non-volatile memory (see 2.2.5.5).
1.2.37.
ShPS-12 provide measuring and sending of measured values in response to a request of the
network controller on:
1) Mains voltage in the range of 150 through 255 V/AC;
2) Battery voltage in the range of 8 through 14.5 V/DC);
3) Output voltage in the range of 8 through 14.5 V/DC;
4) Output current (load current) in the range of 0.1 through 4 A.
Note:
The engineers sought to achieve measurements of high precision; however the measured
values are of an assessment nature with absolute and relative errors of measured values being not
standardized. To carry out precise measurement, certified instruments shall be used.
1.2.38.
A ShPS-12 provides tamper monitoring by means of a tamper switch with contacts closed when the
box door is closed.
1.2.39.
In terms of immunity to electromagnetic interference, ShPS-12 boxes meet the requirements of
Test Severity Level III as per the relevant standards listed in Appendix ‘
Б
’ of GOST R 53325-2012.
1.2.40.
ShPS-12 boxes pass the industrial interference standards prescribed for Class ‘
Б
’ equipment as
per GOST R 30805.22.
Содержание ShPS-12
Страница 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Страница 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Страница 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Страница 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...