13
1.7
Packaging
A ShPS-12 box along with accessory kit and operation documentation is packaged in a separate
cardboard box.
2
Intended Use
2.1
Operating Restrictions
The design of ShPS-12 doesn’t provide its operation in aggressive and / or dusty environments as
well as in explosion hazardous premises.
Correct performance of the ShPS-12 cannot be guaranteed if electromagnetic environment does not
meet the requirements defined in the Section 1.2 of this manual.
2.2
Preparing for Use
2.2.1
Safety Precautions
2.2.1.1.
The ShPS-12 design meets the requirements of electric and fire safety including emergency
operation in accordance with Russian standards GOST 12.2.007.0-75 and GOST 12.1.004-91.
2.2.1.2.
The hazardous items of ShPS-12 are current-carrying circuits connected to 220V AC.
2.2.1.3.
Installation, mounting, and maintenance shall not be carried out until the equipment mount
box is disconnected from the mains power.
2.2.1.4.
Installation and maintenance shall be carried out by professionals qualified for Accident
Prevention of Class III or higher.
2.2.1.5.
Precautions:
It is not allowed using the ShPS-12 box without grounding
a)
Check regularly the ShPS-12’s grounding.
b)
Do not open the ShPS-12 enclosure unless it is disconnected from power supply.
c)
Do not remove the MIP-12 cover.
2.2.1.6.
Before the use, the ShPS-12 shall be grounded to avoid electrical shock. Protection Class is
I as per GOST MEK 60950-2002.
2.2.2
ShPS-12 Design
Please refer to Appendices E, F, and G for ShPS-12 appearance and overall / mounting dimensions.
2.2.3
Mounting the ShPS-12
Installation, mounting, and maintenance shall not be carried out until the equipment mount box is
disconnected from the mains power. Installation and maintenance shall be carried out by professionals
qualified for Accident Prevention of Class III or higher.
2.2.3.1.
Mounting Equipment Inside Box
The Box is used to house and power housed Orion ISS equipment or other devices meant for the DIN-
rail installation. The Appendices B and C show options of how the equipment can be placed in the box
Rails can be moved to a required height for the equipment to be located conveniently. Unused rails can
be removed.
The equipment also can be mounted on the box door (except for ShPS-12 mod.01 and ShPS-12
mod.11). For this purpose, install additional rails using special pins (Appendix D). Additional rails are
included in the MK-1 ShPS mount kit (supplied separately).
Examples of equipment layout can be downloaded at
http://bolid.ru/files/373/566/Primery_raspolozheniya_oborudovaniya.zip
.
If necessary, the equipment can be installed on the wall of the ShPS-12 box; please remove unused
rails for this purpose. Also, please remove transporting tie-wraps from the BK-12 and MIP-12 prior to
operating ShPS-12.
Devices are mounted in the box and connected to the BK-12 terminals by users themselves:
•
Terminals marked as “0” and “+U” are used to connect power supply circuits, but care must be
taken to observe the proper polarity.
•
For ShPS-12, ShPS-12 mod.01, ShPS-12 mod.02 terminals marked as “A1
В
1”, “A2
В
2”… “A7
В
7” are used to connect the RS-485 circuits. External RS-485 circuits must be connected to “A8
B8” terminals.
•
For ShPS-12 mod.10, ShPS-12 mod.11, ShPS-12 mod.12:
−
Terminals marked as “A
В
” are used to connect circuits of the internal RS-485 interface bus
of the box where the BK-12 and devices are installed. The length of the internal RS-485
interface line shall not exceed 10 m for every device.
Содержание ShPS-12
Страница 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Страница 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Страница 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Страница 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...