Terminals  marked  as  “ISO  Port  #1”  (the  first  separate  RS-485  interface)  and  “ISO  Port  #2” 
(the  second  separate  RS-485  interface)  are  used  for  connecting  to  external  RS-485  interface 
circuits. 

If  necessary,  the  user  can  use  the 

ХТ

2  earthing  bus  to  ground  additional  devices  powered  from 

220V /AC.  The 220V power circuits are protected by the common QF1 circuit breaker. 

Upon  erecting  wires  and  cables  passed  through  within  ShPS-12,  ShPS-12  mod.01,  ShPS-12 

mod.10, ShPS-12 mod.11 via upper cable glands, use a sealant (gasket maker) to seal inputs to provide 
IP41 enclosure protection degree. For this purpose, white organosilicone one-part sealant “

ВГО

-1” is 

advised.

 

2.2.3.2.

 

Installing the Box 

Installation  and  connection  of  the  boxes  shall  be  provided  in  accordance  with  design  documents 

developed as specified in effective regulatory documents and approved in the order as intended. 

ShPS-12 can be installed on the walls and other structures of protected premises to avoid exposure 

to the atmospheric precipitation and mechanical damage. 

Mount  the  eye  brackets  on  the  box  using  fasteners  from  the  mounting  kit  provided.  Attach  the 

ShPS-12 on the wall at an easily accessible location. Overall and mounting dimensions can be found in 
Appendix E. 

2.2.4

 

Wiring the ShPS-12 

Install the batteries. 
In accordance with the wiring diagram (Appendix A): 
a)

 

Set the circuit breakers QF1 and QF2 to the OFF position; 

b)

 

Ground  the  ShPS-12

  by  coupling  the 

ХТ

1.3:2

  “

”  input  contact  of  the  terminal  block 

ХТ

1

 

with the ground circuit; 

c)

 

Connect the interface bus and wires to be connected to devices positioned within the box to the 

relevant box terminals; 

d)

 

Connect power wires to the ShPS-12 inlet terminal 

(L line shall be connected to 

ХТ

1.1:2, see 

Appendix A)

e)

 

Mount  batteries  and  connect  them  to  terminals  observing  the  polarity  (the  red  wire  shall  be 

connected to the “+” lead of the battery, while the blue wire shall be connected to   
the “ - ” lead of the battery).

 

 

Connect 

О

-shape  terminal  of  thermal  sensor  to  the  battery  lead  as  shown  in 

Figure 1, according to Appendix A.

 

 

f)

 

Turn on the QF1 and QF2 circuit breakers. 

Note:

 Rated load current is 3 A.  The power supply may operate a short period 

under  3.5A  (see  1.2.5)  in  case  of  activation  of  sound  alarm  devices,  fire-fighting 
systems, actuating devices, etc. 

Warning!  In  case  of  long  operation  at  overload,  the  battery  charging  process  is  terminated, 

and the battery starts discharging even if the mains voltage is available.  If the total load current 
exceeds  4A,  the  power  supply  unit  turns  OFF  output  voltage  and  the  equipment  is left without 
the power.

 

Recommended cross sections of wires connected to the ShPS-12 box are as follows: 

o

 

To 220V mains power (to 

ХТ

1 terminal): 1.5 to 2.5 mm

2

 for multi stranded wires or 1 to 2 mm

2

 

for solid wires; 

o

 

To  RS-485  line  (the  BK-12  unit):  0.12  to  2  mm

2

  for  multi  stranded  wires  or  0.4  to  1  mm

2

  for 

solid wires; 

o

 

To connect loads (the BK-12 unit): 0.5 to 2 mm

2

 for multi stranded wires or 1 to 2 mm

2

 for solid 

wires  with  taking  into  account  voltage  drops  at  maximum  load  current  (minimal  permitted  voltage 
when loaded). 

When installation is completed, run the test of system operations in the Fire Alarm condition during 

one hour to check whether the ShPS-12 is capable to provide functionality of the installed equipment 

 

WARNING! 
When connecting external  220 V mains supply voltage to the XT1 terminal block, 

care must be taken to observe the correct connection of the Line and Neutral wires. 
Make  the  connections  in  accordance  with  Appendix  A.  The  connection  diagram  is 
also located on the inner side of the ShPS-12 door 

Figure 1 

Содержание ShPS-12

Страница 1: ...SрPS 12 FIRE EQUIPMENT MOUNT BOXES WITH BACKUP BATTERY POWER SUPPLIES ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 User s Manual ...

Страница 2: ... 13 2 2 4 Wiring the ShPS 12 14 2 2 5 Programming the ShPS 12 15 2 2 6 Usage 16 2 2 7 Performance Testing 17 2 2 8 Extreme Situation Actions 19 2 2 9 Troubleshooting 19 3 Maintenance 19 3 1 General 19 3 2 Safety Precautions 19 3 3 Maintenance Procedures 20 3 4 Operability Testing 20 3 5 Technical Examination 20 3 6 Preservation Depreservation Represervation 20 4 Repair 20 5 Storage 20 6 Transporti...

Страница 3: ... Signal 10 Signal 20P S2000 4 S2000 KDL S2000 KPB S2000 SP1 S2000 PI S2000 KDL 2I Rupor mod 02 S2000 PGE S2000 PGE mod 01 S2000 Ethernet S2000 RPI and other devices mountable on a 35 mm top hat DIN rail in accordance with GOST R MEK 60715 2003 1 1 3 ShPS 12 mod 10 ShPS 12 mod 11 and ShPS 12 mod 12 are intended for operation with Sirius Fire Alarm Control Panel and C2000M Monitoring and Control Pan...

Страница 4: ... or similar 12 V 17 Ah 2 batteries 1 2 4 Output voltage while powered by mains 13 6 0 6 V batteries 13 5 9 5 V 1 2 5 Rated maximum load current 3 A 3 5 A 1 2 6 Outputs for powering devices consuming 12 V and installed within ShPS 12 7 1 2 7 Maximum current per a single output 12V dc 0 65 A 1 2 8 Outputs for connecting RS 485 interface lines installed within ShPS 12 7 1 2 9 For ShPS 12 ShPS 12 mod ...

Страница 5: ...5 interface messages about presence of relevant voltages faults battery dis charge bad battery health and battery disablement and tampering 1 2 33 The built in PSU of ShSP 12 is ready to operate after 6 seconds upon powering up 1 2 34 A ShPS 12 features a Remote Fault Output a solid state relay with the following parameters maximum switched voltage current is 80 V 50 mA maximum resistance of close...

Страница 6: ...ons Manual 1 Note No battery is included in the standard delivery 1 4 Arrangement and Operation 1 4 1 A ShPS 12 is assembled within a metal enclosure The enclosure consists of a cabinet and a key lockable door On the outer surface of the door there are light indicators to indicate the ShPS 12 conditions The cabinet houses the MIP 12 power supply module the BK 12 switch unit for connections and cir...

Страница 7: ... process does not start If for the ShPS 12 box no measurement of battery capacity was carried out during operation and the ShPS 12 box is requested for backup operation time and time to measure the capacity it will calculate these details on the assumption of installed batteries of 17 Ah capacities and the output current value f If an unacceptable output overload or short circuit fault occurs the ...

Страница 8: ...and current values to charge the batteries Power Failed the mains power being applied to the box the ShPS 12 does not provide functions according to 1 2 4 Power Restored the mains power being applied to the box the ShPS 12 provides functions according to 1 2 4 Battery Fault voltage of any of the batteries is lower than 7V or batteries are not connected Battery Test Error battery internal resistanc...

Страница 9: ...PUT ADC Select the Input ADC item using the 43 buttons and click or click 2 for quick navigation ADDRESS _ Enter the device address 1 to 127 or select it from the menu using the 43buttons and press INPUT _ Enter the required input number or select it from the menu using the 4 3buttons and press The requested data are presented in the form of text and specific ADC values Input Information on the S2...

Страница 10: ... adjusted in the appeared dialog box The ShPS 12 will adjust the selected values to the values of mains voltmeter after saving configuration and reset 1 4 3 Operation of ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 under Sirius Panel To request conditions as well as to view various values measured by the ShPS 12 by means of the Sirius Fire Alarm Control Panel do the following as stated in the Siri...

Страница 11: ...lity Firmware Update The last version of this program is available online at the address of http bolid ru To switch the BK 12 RS485 to the programming mode please close the jumper circuit ХР5 PROG on the board of the BK 12 RS485 The programming mode is indicated by two board LEDs blinking once per second Only one of the separate RS 485 interfaces is used for updating 1 5 Measuring Instruments Tool...

Страница 12: ...be carried out until the equipment mount box is disconnected from the mains power Installation and maintenance shall be carried out by professionals qualified for Accident Prevention of Class III or higher 2 2 3 1 Mounting Equipment Inside Box The Box is used to house and power housed Orion ISS equipment or other devices meant for the DIN rail installation The Appendices B and C show options of ho...

Страница 13: ...all be connected to ХТ1 1 2 see Appendix A e Mount batteries and connect them to terminals observing the polarity the red wire shall be connected to the lead of the battery while the blue wire shall be connected to the lead of the battery Connect О shape terminal of thermal sensor to the battery lead as shown in Figure 1 according to Appendix A f Turn on the QF1 and QF2 circuit breakers Note Rated...

Страница 14: ...longer than 1sec Reset network address to set default address 127 Reset battery life counter and measured capacity when battery replaced 2 2 5 4 If the network controller is powered from another power supply the circuits 0 V of the ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 box and network controller shall be connected as a single circuit 2 2 5 5 The programmable parameters are described in Table 5 and...

Страница 15: ...run ning right after powering on the ShPS 12 or reboot Turn On Turn Off Turn On for a Time Turn Off for a Time Turn Off 2 Relay Activa tion Time Time for the relay to be turned on off for the com mands Turn On for a Time and Turn Off for a Time 0 8191 875 s 8191 875 s 3 Relay Control Option Selection of monitored pa rameters to activate the relay control program 1 All parameters but for communi ca...

Страница 16: ...acity Measurement To make the capacity measurement available the battery charge level shall be more than 80 Note The battery charge volume being less than 80 the ShPS 12 cannot measure the capacity of installed batteries a To measure the ShPS 12 battery capacity using the S2000M panel please use the Test Detector function see S2000M Users Guide When initiating a testing command please specify 0 fo...

Страница 17: ... ShPS 12 load 2 Time Limited The test is to be completed at the end of the time period given in the field below This test option is recommended if you want to get info on the ShPS 12 functionality in the backup mode for the time specified If batteries are discharged lower than 80 during the Time Limited test the ShPS 12 can calculate the actual capacity of the batteries installed in the ShPS 12 bo...

Страница 18: ...cantly reduced bat tery capacity 2 Battery leads oxidation or loosened battery contacts 1 Replace batteries 2 Clean leads tighten wire connections of the battery ShPS 12 issues the Ser vice Required message Battery lifetime expired Replace the batteries and reset the lifetime counter Lost communications between the ShPS 12 and network controller 1 Failed connection between the ShPS 12 and controll...

Страница 19: ... rules of mounting and operation is not a reason for claims and warranty repair Claims should be submitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Phone fax 7 495 775 71 55 PBX E mail info bolid ru In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 5 Storage Storage in ...

Страница 20: ... the manufacturer s date of production 9 Certification Information 9 1 ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 meet the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and are covered by Conformity Declaration ЕАЭС RU Д RU НА74 В 00197 19 9 2 ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mo...

Страница 21: ...5 A1 14 B1 13 0 12 U 11 A2 10 B2 9 0 8 U 7 A3 6 B3 5 0 4 U 3 A4 2 B4 1 B A 17 18 ХТ2 Neutral Line ХТ1 3 ХТ1 2 ХТ1 1 ХТ3 3 ХТ3 2 N L Neutral Earthling Blue Red Fault relay output 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 17 18 0 V V 0 U A6 B6 0 U A5 B5 A8 B8 0 U A7 B7 Line Blue Red 1 8 ...

Страница 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...

Страница 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...

Страница 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...

Страница 25: ...Example of Arranging Equipment on the Door of ShPS 12 ShPS 12 mod 02 ShPS 12 mod 10 or ShPS 12 mod 12 using MK 1 ShPS Mounting Kit S2000 4 6 7 8 9 10 SIGNAL 10 S2000 KDL RS 485 LOOP S2000 KPB COM MASS PRES READY READY READY READY ...

Страница 26: ...27 Appendix E Overall and Mounting Dimensions For ShPS 12 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 12 320 103 320 140 Шпильки для установки реек DIN Rail Pins ...

Страница 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...

Страница 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...

Страница 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...

Отзывы: