19
In case of successive receiving of this command, the ShPS-12 executes it and issues the Test
Starts event. The procedure of capacity measurement completes automatically. Upon completing the
procedure the ShPS-12 issues the Test Ends event.
d)
To measure the battery capacity without using commands over RS-485, conduct the
following:
1)
Make sure the batteries are charged higher than 80% (indicated by steady lit BAT LED);
2)
Turn off the ShPS-12 input power;
3)
Upon receiving a Battery Low message, apply input power, and the ShPS-12 will calculate
the resulted capacity.
2.2.8
Extreme Situation Actions
2.2.9
Troubleshooting
Table 7
Faults
Causes
Corrective Actions
ShPS-12 failed to be
turned on being powered
by mains
1. The QF1 circuit breaker
failed.
2. Wiring faults.
3. Long time overload at the
output of the ShPS-12
1. Measure the voltage on mains circuit be-
fore and after the QF1 circuit breaker.
2. Repair wiring faults.
3. Power off the ShPS-12 for two or more
minutes, and then power it on again.
ShPS-12 failed to be
turned on being powered
by batteries
The battery voltage is lower
than 10 V
Check the battery voltage. Charge or replace
batteries as required
ShPS-12 transmits Bat-
tery Test Error message
1. Significantly reduced bat-
tery capacity.
2. Battery leads oxidation or
loosened battery contacts
1. Replace batteries.
2. Clean leads; tighten wire connections of
the battery.
ShPS-12 issues the Ser-
vice Required message
Battery lifetime expired
Replace the batteries and reset the lifetime
counter
Lost communications
between the ShPS-12 and
network controller
1. Failed connection between
the ShPS-12 and controller.
2. Wrong connection of
transmission path to A and B
interface contacts
1. Restore connection; meet the require-
ments as to 2.2.5.4 of this manual.
2. Swap the transmission path wires con-
nected to A and B contacts of the RS-485
interface
The controller transmits
the Communication Lost
event
1. Open-circuit failure on the
transmission path.
2. The ShPS-12 has turned
off the transceiver due to a
low battery charge
1. Recover connection.
2. Take measures to recover mains supply
3
Maintenance
3.1
General
ShPS-12 shall be maintained in line with the following schedule:
Table 8
Task Description
Frequency
Visual inspecting of the ShPS-12 box
Monthly
Inspecting of proper operation of ShPS-12
powered from both power supplies
Six-monthly
3.2
Safety Precautions
The product shall be maintained by personnel qualified for the Electrical Safety of Level III or
higher.
Warning
!
If sparks, fire, smoke, or smell of burning is found at the installation site of the
product, the product must be de-energized and sent for repair
Содержание ShPS-12
Страница 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Страница 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Страница 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Страница 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...
Страница 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...