10 AC LINE FUSING
This drive does not contain AC line fuses. Most electrical codes require that each ungrounded con-
ductor contain circuit protection.
Do not fuse neutral or ground connections.
It is recommended to
install a fuse (Littelfuse 326, Buss ABC, or equivalent) or a circuit breaker in series with each
ungrounded conductor.
Do not fuse motor leads.
For the recommended fuse size, see Table 1,
on page 14. Wire the drive in accordance with the National Electrical Code requirements and other
local codes that may apply to the application.
For
Forward Enable Operation,
wire the switch to the white and black wires. For
Reverse
Enable Operation,
wire the switch to the red and black wires. When the switch is closed, the
drive will run. When the switch is opened, the drive will stop.
FIGURE 21 – ENABLE SWITCH CONNECTION
Jumper Removed
Connector Installed for
Forward Enable Switch
Connector Installed for
Reverse Enable Switch
CON2
F - S - R
(Close to Run)
Red *
(Open to Stop)
Black
White
Enable Switch
CON2
Forward
(Close to Run)
Red
(Open to Stop)
Black
White*
Enable Switch
CON2
Reverse
*For Forward Enable Switch connection, the red wire is not used. For Reverse Enable Switch connection, the white wire is
not used.
The unused wire must be insulated or it may be cut off at the connector.