5.4.4 Connection to the hot water coil
Refer to the dimensional drawings for the position and size of the water connections.
Please observe the following guidelines:
- use copper or steel pipes;
-
adequately insulate the pipes;
-
install shut-off valves in/out of the unit;
- install a thermometer and a pressure gauge at the input and output of the unit.
Should the fluid contained in the hydraulic system be able to fall to near or below zero Celsius, add an appro
-
priate percentage of antifreeze.
5.4.5 Connection to the humidifier
Where present, the humidifier must be supplied with untreated mains water, preferably filtered from impurities and / or wa
-
ste. The diameters of the couplings are reported in the dimensional drawings.
We recommend that the drain duct should consist of a non-electrically conductive material.
The water discharged from the humidifier can reach 100 ° C.
It is compulsory to implement a syphon in order to drain the water from the humidifier.
Absolutely do not fill the humidifier with demineralised or softened water.
Further information concerning installation may be found in the "Humidifier" chapter and in the humidifier manual enclosed
with the unit’s documentation.