ACCEPTABLE CABLE JACKET RANGE:

.118 - .255 INCH .(    3,0 - 6,5 MM)

EXTERNAL INPUT CABLE

5.3 External Input Signal Connections 

 

The pump will accept a variety of external control input signals; 4-20 mA , 
0-10 VDC, TTL, CMOS, AC Sine Waves, Contact Closures, Hall Effect, 
NPN. The 4-20mA and 0-10 VDC loops must be powered. 
All wiring connections are to be made inside of the junction box located on 
the side of the pump.  Special connectors are not required. A liquid-tite 
connector is supplied and should be used for the external signal cable.  The 
signal input wires are color coded to the type of signal being used.

Page 6

Page 7

INPUT

VOLTAGE

115V 60Hz

220V 50Hz

HOT

LEADWIRE

NEUTRAL

LEADWIRE

GROUND

LEADWIRE

230V 60Hz

YELLOW

YELLOW

YELLOW

BLUE

BROWN

RED

GREEN

GREEN

GREEN

MOTOR LEADWIRES

SIGNAL INPUT WIRE COLOR CODES

  CIRCUIT BOARD CONNECTIONS

 AC

MOTOR

Neutral (blue/brown/red)

Hot (yellow)

Ground (green)

Ground (green)

Common

Hot

AC

Input

Power

Power Circuit Board

(Top view)

Protector Fuse

2 Amps, 250 Volt AC

(little Fuse #235002

 or Equivalent)

R R

2A

250VAC

T3

T2

T1

T4

LINE

HOT

LINE

NEUTRAL

MOTOR

NEUTRAL

MOTOR

SWITCHED

115V 50/60Hz

INPUT VOLTAGE 
RESISTOR PLACEMENT

220V 50/60Hz
230V 50/60Hz

R R

R

MA = BLUE

GND = BLACK

RELAY = PURPLE (2)

VDC = ORANGE

VS = RED (+17V DC)

PLS = WHITE

JUNCTION BOX

LIQUID-TIGHT
CONNECTOR

MTR = BROWN

Alarm Relay

3A/125VAC

N/C

COM

N/O

Purple connection wires

Default is N/O

VS
VDC
MA
MTR
GND
PLS

CN3

VS

FVS
GND

TFD
GND

FVS+

CN4

Control Circuit Board

(Back view)

Program Disable Jumper

 - Located on front of Control board.

Un-installed = enable front panel programming (default)
Installed = disable front panel programming

External input connections

6 Wire bundle to junction box

Flow verification sensor connector

3 Wire bundle to junction box.

red/black/yellow

Tube failure detection sensor connector

2 Wire bundle to pump head sensor

(A-100N series pumps only)

WIRE COLOR CODE

INPUT TYPE

MOTOR ON SIGNAL

5-20V DC open collector output

closed while motor is energized

FLOW VERIFICATION SENSOR

4-20 mA

0-10 VDC

ALARM RELAY

BROWN (+)

 & 

BLACK (-)

PURPLE

 & 

PURPLE

WHITE (+)

 & 

BLACK

 

(-)

BLUE

 

(+)

 & 

BLACK

 

(-)

TTL, CMOS

ORANGE (+)

 & 

BLACK

 

(-)

RED/WHITE (+ 

20VDC) & 

BLACK (-)

 & 

YELLOW 

(signal)

CONTACT (10v @ 2 mA max)

HALL EFFECT, NPN

RED (+)

 & 

WHITE (-)

C-1100E

C-1100E

PADDLEWHEEL SENSOR SIGNAL INPUT WIRING

PADDLEWHEEL SENSOR

WIRE COLOR CODE

BLUE-WHITE 

PADDLEWHEEL 

SENSOR TYPE

MODEL FH

HALL EFFECT SENSOR

BLACK

 

(-)

RED (+)

PUMP INPUT

WIRE COLOR CODE

MODEL FC

AC SINE WAVE SENSOR

BARE (signal)

BLACK

 

(-)

RED (+ 20VDC)

WHITE (signal)

BLACK

 

(-)

RED (+)

BLACK

 

(-)

WHITE (+)

Содержание CHEM-FEED C-1100E

Страница 1: ...2649 USA Phone 714 893 8529 FAX 714 894 9492 E mail sales blue white com or techsupport blue white com Website www blue white com Blue White Industries Ltd R INJECTOR MODEL C 1100 MODEL E POSITIVE DIS...

Страница 2: ...10 6 3 Mode 0 FVS System set up 10 6 4 Mode 1 Manually Adjusting the output 13 6 5 Mode 2 4 20 mA input 14 6 6 Mode 3 0 10 VDC input 16 6 7 Mode 4 Frequency Hz input 19 6 8 Mode 5 Pulse input Batch 2...

Страница 3: ...a high system pressure up to 150 PSI 10 4 bar In addition to the front mounted mechanical flow rate adjustment the C 1100 Model E unit is equipped with an external input control circuitry which allows...

Страница 4: ...should be sturdy Keep the tank covered to reduce fumes Do not mount the pump directly over your tank Chemical fumes may damage the unit Mount the pump off to the side or at a lower level than the chem...

Страница 5: ...7 Circuit Board Connections diagram for details The pump is supplied with a ground wire conductor and a grounding type attachment plug power cord To reduce the risk of electric shock be certain that t...

Страница 6: ...50Hz HOT LEADWIRE NEUTRAL LEADWIRE GROUND LEADWIRE 230V 60Hz YELLOW YELLOW YELLOW BLUE BROWN RED GREEN GREEN GREEN MOTOR LEADWIRES SIGNAL INPUT WIRE COLOR CODES WIRE COLOR CODE INPUT TYPE MOTOR ON SIG...

Страница 7: ...GND BLACK RELAY PURPLE 2 VDC ORANGE VS RED 17V DC PLS WHITE JUNCTION BOX LIQUID TIGHT CONNECTOR MTR BROWN Alarm Relay 3A 125VAC N C COM N O Purple connection wires Default is N O VS VDC MA MTR GND PL...

Страница 8: ...ing is designed to install directly into either 1 4 or 1 2 female pipe threads This fitting will require periodic cleaning especially when injecting fluids that calcify such as sodium hypochlorite See...

Страница 9: ...How To Operate The Pump 6 1 How to adjust the output manual stroke adjustment The Pump flow rate can be adjusted within a range of 5 100 of maximum output 20 1 turndown ration by means of a mechanica...

Страница 10: ...ton initiates the programming mode The ARROW next to the word PROGRAM will blink FIELD Button In the programming mode selects the digit to be changed DIGIT Button In the programming mode increases the...

Страница 11: ...lue of 000 seconds disables the FVS system The pump will stop and the alarm mode activated if no pulses are received by the pump and the alarm delay time period has ended Press the STAND BY button twi...

Страница 12: ...cuitry will automatically return to the run mode The TFD system The TFD icon will blink The TFD system is only used on A 100N series peristaltic pumps The word ON will display indicating the TFD syste...

Страница 13: ...tly RUN PROGRAM STAND BY PRIME MINIMUM MAXIMUM 1 199 9 MODE TOT T SEC RUN PROGRAM STAND BY PRIME MINIMUM MAXIMUM 1 42 5 MODE ON T SEC selected time unit icon will be displayed The current total time s...

Страница 14: ...14 16 18 20 0 2 4 6 8 Pump Run Time Sec Milliamp input mA Page 14 Set the pump for mode 2 Press the MODE button until MODE 2 is shown on the LCD display Enter the programming mode At the same time pre...

Страница 15: ...ogramming screen and enter the total time programming screen The total time TOT T icon will blink The currently selected time unit icon will be displayed The current total time setting will be display...

Страница 16: ...OGRAM STAND BY PRIME MINIMUM MAXIMUM 3 00 0 MODE ON T SEC Set the pump for mode 3 Press the MODE button until MODE 3 is shown on the LCD display Enter the programming mode At the same time press the R...

Страница 17: ...nimum programming screen and enter the total time programming screen The total time TOT T icon will blink The currently selected time unit icon will be displayed The current total time setting will be...

Страница 18: ...MODE 4 is shown on the LCD display Enter the programming mode At the same time press the RUN STANDBY button and the MODE button A blinking ARROW will point to the word PROGRAM indicating the program...

Страница 19: ...nimum programming screen and enter the total time programming screen The total time TOT T icon will blink The currently selected time unit icon will be displayed The current total time setting will be...

Страница 20: ...ng screen The HZ icon will blink A blinking ARROW will appear next to the word MAXIMUM The current Hz setting will be displayed and the left most selected digit will blink icon will be displayed The c...

Страница 21: ...stalled in the graduated cylinder 4 Run the pump until all air is removed from the suction line and the solution enters the discharge tubing If the pump does not easily prime remove the discharge tubi...

Страница 22: ...itting the Footvalve Strainer and the pump head valves The frequency will depend on the type and severity of service Inspect and replace the pumphead valves as required When changing the diaphragm the...

Страница 23: ...Page 23 C 1100E PUMP HEAD AND VALVE EXPLODED VIEW...

Страница 24: ...T OFF P2 4 20 mA NOR MAL P3 20 4 mA INVE RTE D P4 0 10 VDC NOR MAL P5 10 0 VDC INVE RTE D P6 SLO W PUL SE X 1 P7 FAS T PUL SE X 100 99 SEC CYC LE ADJ UST CYC LE WHE N LIT ADJ UST CYC LE WHE N LIT 500...

Страница 25: ...de Bearing 2 21 76000 172 Stirr up 1 22 90002 017 Dial Knob 1 23 90011 168 Screw 6 x 62 PH oval A 4 24 90011 121 Thumb Screw 6 32 x 1 125 1 25 71000 363 Cover Cam S A C 1100 1 26 90006 597 Gasket Top...

Страница 26: ...al label and the sales invoice or receipt The serial label must be on the pump and the pump must be accompanied by the sales invoice or receipt to obtain warranty coverage The warranty status of the p...

Страница 27: ...ahassee FL 32304 850 575 9618 Jerry Lee Chemical Co 3407 W Old Fairfield Drive Pensacola FL 32505 904 432 9929 Picard Chemical 1670 S Congress Avenue W Palm Beach FL 33406 561 965 3434 ILLINOIS Mullar...

Страница 28: ...v 3 03 17 2020 5300 Business Drive Huntington Beach CA 92649 USA Phone 714 893 8529 FAX 714 894 9492 E mail sales blue white com or techsupport blue white com Website www blue white com Blue White Ind...

Отзывы: