Install the FVS Flow Sensor -
The Flow Verification Sensor
(FVS) should be installed on the
discharge (outlet) pump head
valve. The sensor includes a
PVC tubing insert, located
inside the sensor’s female
thread connection, that is
designed to seal the sensor onto
the pump tube inlet adapter.
Thread the sensor onto the
pump tube until the tubing
insert is snug against the pump
tube inlet fitting - do not over-
tighten.
Connect the red/white, black,
and white wires from the sensor
to the red, black, and yellow
wires located in the pump’s
junction box. See page 7.
6.3 MODE 0 - FVS system set-up (sensor sold separately)
!
(FVS) Flow Verification System
The C-1100E is equipped with a
-
Flow Verification System
which is designed to stop the pump and provide a
contact closure output in the event the sensor does not detect chemical
during pump operation. This could indicate a clogged injection fitting,
empty chemical solution tank, loose tubing connection, etc.
To allow the pump to clear any gasses that may have accumulated during
stopped operation, an alarm delay time value from 1-256 seconds must be
programmed (An alarm delay value of 000 seconds disables the FVS
system). The pump will stop, and the alarm mode activated, if no pulses are
received by the pump and the alarm delay time period has ended. Press the
STAND-BY button twice to clear the alarm and restart the pump. The Flow
Verification Sensor is sold as an optional accessory.
6.2 Electronic Pump Output
Controls
-
Open the control panel door by sliding the
upper and lower slide clamps to the left.
!
RUN/STANDBY
Button -
+
Press to start and stop the pump. The
ARROW
next to the word
RUN
will light
when in the run mode. The
ARROW
next
to the word
STAND-BY
will blink when in
the stand-by mode.
+
Press to clear
ALARM.
+
When pressed with the FIELD Button, initiates a 99 second prime cycle
which temporarily overrides the mode setting and runs the pump motor at
100% speed. The
ARROW
next to the word
PRIME
will blink.
+
When pressed with the DIGIT button, resets the 500 hour service warning
timer to zero.
+
When pressed with the MODE button, initiates the programming mode.
The
ARROW
next to the word
PROGRAM
will blink.
!
FIELD
Button -
+
In the programming mode, selects the digit to be changed.
!
DIGIT
Button -
+
In the programming mode, increases the selected digit.
+
When pressed with the MODE Button, toggles the display from operating
time cycle values to input signal value.
!
MODE
Button -
+
Used to select one of five operating modes.
Mode 0
- FVS system set-up
Mode 1
- Manual Adjustment (external input disabled)
Mode 2
- 4-20mA input
Mode 3
- 0-10VDC input
Mode 4
- Frequency input adjusts cycle on-time
Mode 5
- Pulse input count = single batch time
RUN
STANDBY
RUN
FIELD
DIGIT
MODE
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
INPUT MODES
1 - MANUAL
2 - 4-20mA
3 - 0-10VDC
4 - 0-1000 Hz
PROGRAM
RESET SERVICE
PRIME
DISPLAY
DIGITAL TIMER PUMP
1
VDC
SERVICE
1000
ALARM
mA
Hz
MODE
TFDFVS
ON-TTOT-TSECMINHRDAY
5 - PULSE (BATCH)
Confirm the FVS flow range -
The Flow
Verification Sensor (FVS) will only function
within its operating range. Sensor model FV-100-
6V has an operating range of 30-300 ml/min (1-10
oz/min). If the pump’s output is less than 30
ml/min (0.5 ml/sec), the sensor will not detect
chemical and a signal will not be sent to the pump.
OPERATING
FLOW RANGE
(ml/min)
30-300
FV-100-6V
100-1000
FV-200-6V
200-2000
FV-300-6V
300-3000
FV-400-6V
500-5000
FV-500-6V
700-7000
FV-600-6V
SENSOR
MODEL
NUMBER
Insert Tubing Seal
CAUTION
ADJUST WHILE RUNNING
DISCHARGE LINES MAY BE
UNDER HIGH PRESSURE. USE
CARE TO PROTECT YOURSELF
WHEN DISCONNECTING.
MAX
MIN
1
2
3
4
5
6
7
8
9
LOOSEN THE LOCK SCREW
TURN KNOB TO DESIRED SETTING
RE-TIGHTEN THE LOCK SCREW
RUN
STANDBY
RUN
FIELD
DIGIT
MODE
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
INPUT MODES
1 - MANUAL
2 - 4-20mA
3 - 0-10VDC
4 - 0-1000 Hz
PROGRAM
RESET SERVICE
PRIME
DISPLAY
DIGITAL TIMER PUMP
1
VDC
SERVICE
1000
ALARM
mA
Hz
MODE
TFDFVS
ON-TTOT-TSECMINHRDAY
5 - PULSE (BATCH)
Outlet Adapter
FVS Sensor
C-1100E
C-1100E