0x309H
Current imbalance trip delay
Range: 0 ~ 50.0sec
0x30AH
Under load threshold
Under load protection
Range: 20 ~ 100%Ie
0x30BH
Under load trip delay
Range: 0.5 ~ 50.0sec
0x30CH
Stall threshold
Stall protection
Range: 100 ~ 800%Ie
0x30DH
Stall trip delay
Range: 0.5 ~ 50.0sec
0x30EH
Residual current threshold
Ground fault protection
Range: 10 ~ 100%IΔn
0x30FH
Ground fault trip delay
Range: 0.1 ~ 50.0sec
0x310H
Overvoltage threshold
Overvoltage protection
Range: 105 ~ 150%Ue
0x311H
Overvoltage trip delay
Range: 0.1 ~ 50.0sec
0x312H
Under voltage threshold
Under voltage protection
Range: 45 ~ 95%Ue
0x313H
Under voltage trip delay
Range: 0.1 ~ 50.0sec
0x314H
tE setting
Range: 1 ~ 15
0x315H
Protection function status
0:
disable
1:
enable
BIT0:
Start over time
BIT1:
Over load
BIT2:
Phase failure
BIT3:
Jam
BIT4:
Current imbalance
BIT5:
Under load
BIT6:
Stall
BIT7:
Ground fault
BIT8:
tE
BIT9:
Over voltage
BIT10:
Under voltage
BIT14:
Overload reset mode
0:
manual
1:
automatic
0x316H
Protection function mode
0 for Alarm;
1 for Trip
BIT0:
Start over time
BIT1:
Over load
BIT2:
Phase failure
BIT3:
Jam
BIT4:
Current imbalance
BIT5:
Under load
BIT6:
Stall
BIT7:
Ground fault
BIT8:
tE
BIT9:
Over voltage
BIT10:
Under voltage
0x800H
Empty SOE records
Input command:
0A0A