User Manual
Tel: +0086-023-67628702 Email:[email protected]
www.cqbluejay.com
Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China - 21 -
Overload inverse time curve
Overload inverse time curve quick select chart
( t unit: sec)
K
I/Ie
10
25
60
75
100
125
250
300
500
750
1000
1200
1.1
47.62
119.05 285.71 357.14 476.19 595.24
1190.48 1428.57 2380.95 3571.43 4761.90 5714.28
1.2
22.73
56.82
136.36 170.45 227.27 284.09
568.18
681.82
1136.36 1704.55 2272.73 2727.27
1.3
14.49
36.23
86.96
108.70 144.93 181.16
362.32
434.78
724.64
1086.96 1449.28 1739.13
1.4
10.42
26.04
62.50
78.13
104.17 130.21
260.42
312.50
520.83
781.25
1041.67 1250.00
1.5
8.00
20.00
48.00
60.00
80.00
100.00
200.00
240.00
400.00
600.00
800.00
960.00
2.0
3.33
8.33
20.00
25.00
33.33
41.67
83.33
100.00
166.67
250.00
333.33
400.00
2.5
1.90
4.76
11.43
14.29
19.05
23.81
47.62
57.14
95.24
142.86
190.48
228.57
3.0
1.25
3.13
7.50
9.38
12.50
15.63
31.25
37.50
62.50
93.75
125.00
150.00
3.5
0.89
2.22
5.33
6.67
8.89
11.11
22.22
26.67
44.44
66.67
88.89
106.67
4.0
0.67
1.67
4.00
5.00
6.67
8.33
16.67
20.00
33.33
50.00
66.67
80.00
4.5
0.52
1.30
3.12
3.90
5.19
6.49
12.99
15.58
25.97
38.96
51.95
62.34
5.0
0.42
1.04
2.50
3.13
4.17
5.21
10.42
12.50
20.83
31.25
41.67
50.00
5.5
0.34
0.85
2.05
2.56
3.42
4.27
8.55
10.26
17.09
25.64
34.19
41.03
6.0
0.29
0.71
1.71
2.14
2.86
3.57
7.14
8.57
14.29
21.43
28.57
34.29
6.5
0.24
0.61
1.45
1.82
2.42
3.03
6.06
7.27
12.12
18.18
24.24
29.09
7.0
0.21
0.52
1.25
1.56
2.08
2.60
5.21
6.25
10.42
15.63
20.83
25.00
7.2
0.20
0.49
1.18
1.48
1.97
2.46
4.92
5.90
9.83
14.75
19.67
23.60
7.5
0.18
0.45
1.09
1.36
1.81
2.26
4.52
5.43
9.05
13.57
18.10
21.72
8.0
0.16
0.40
0.95
1.19
1.59
1.98
3.97
4.76
7.94
11.90
15.87
19.05
Protection mode
OFF / Alarm / Trip
K factor value
10 ~ 1200
Cool down timer
1 ~ 1200 min
Failure reset
Manual / Auto
Cool down timer:
After motor stop, the cool down timer countdown to simulated the motor cools to a safe state
process; the definition of the cooling time is to reach steady state of ambient temperature (the
maximum allowable temperature) when motor overload trip. Typically, cool timer can set to 30
minutes as heat capacity values decreased from 100% to 15%.