180-CL29-SP v1.00
March 12, 2019
Page 23
Clarity CL29 SP
INSTALLATION CLEARANCES
OPERATION OF THIS HEATER WHEN NOT CONNECTED TO A PROPERLY INSTALLED AND
MAINTAINED VENTING SYSTEM CAN RESULT IN CARBON MONOXIDE (CO) POISONING AND
POSSIBLE DEATH
Max. lentil
bar depth
A
9.25”
235 mm
Height
B
20”
508 mm
Depth
C
15 1/2”
394 mm
Width (rear)
D
22”
559 mm
Width (front)
E
29 1/8”
740 mm
MINIMUM FIREPLACE DIMENSIONS
The minimum fi replace dimensions the this insert are in the following diagrams and chart:
MINIMUM CLEARANCES TO COMBUSTIBLES
A Unit to sidewall.
4.5” (115 mm)
B
Bottom of unit to underside of mantle.
*With S.Z4974 mantle shield.
52" (1321 mm)
*42" (1067 mm)
C Maximum mantle depth.
12" (305 mm)
D Minimum ceiling clearance from bottom of unit. 67.5" (1715 mm)
NOTE: CHECK LOCAL CODES FOR FLOOR REQUIREMENTS.
THIS FIREPLACE IS SUITABLE ONLY FOR INSTALLATION IN A
MASONRY OR FACTORY BUILT FIREPLACE.
COMBUSTIBLE
FLOOR IN FRONT
CAN BE LEVEL
WITH HEARTH AND
CL29 LEVELING
BOLTS MUST
BEINSTALLED.