KOMFORT LE
CONTROL PANEL MOUNTING
The control panel incorporates a room temperature sensor that must be
located at least 1 m away from the heating appliances, doors and windows.
Fix the control panel on the wall with supplied screws.
Connect the control panel to the unit via the supplied four-wire data
cable, max. 10 m. Do not route the data cable between the control panel and
the unit close to power cables, keep the minimum distance 150 mm.
The control panel is supplied assembled and connected to the unit. In
case of the control panel re-assembly follow this sequence:
1. Disassemble the control panel, fig. 9:
1.1 Press the latches to open the control panel case.
2.1 Disconnect the cable from the terminal block.
3.1 Remove the data cable.
2. Route the cable to the control panel installation place.
3. Install the control panel, fig. 10 as follows:
3.1. Route the cable through the opening in the bottom cover.
3.2. Fix the bottom cover of the control panel in the installation place.
The screw head must not be in contact with the control panel circuit board,
otherwise the equipment may be damaged!
3.3. Strip the cable for ~20 mm.
3.4. Strip the wires for ~6 mm.
3.5. Connect the wires to the terminal block in the circuit board in
compliance with the designations and the wire colour:
1
2
3
Fig. 9. Control panel disconnection
yellow
+
green
В
brown
А
white
1
2
3
4
yellow
+
green
B
brown
A
white
┴
3.6. Press the latches to close the control panel cover.
4. Route the cable through the cable lead-in the in the control panel case
and connect the wires to the contacts in the terminal block, fig. 10.
Fig. 10. Control panel mounting