KOMFORT LE

Control system general description.

The unit is controlled with a wall-mounted control panel, fig. 12. The 

communication circuit is presented with a four-wire data cable up to 10 m.

  The control system controls the air flow of the supply and extract fan 

in three speed stages:  

• 

low speed is used for ventilation in non-residential premises during 

weekend or in residential premises during night time. 

• 

medium speed is used for the rated ventilation mode. 

• 

high speed is used for high-power ventilation with extra air flow. 

  The temperature sensors are used for correct selection of the operation 

mode and maintaining set air temperature in the air duct. 

  The temperature sensor is integrated into the control panel and is used 

to maintain the set indoor temperature at set air flow or in compliance with 

the selected service function, see below. 

  The correct operation mode selection as well as indication of the 

current parameters as indoor temperature, set temperature, fan speed stage, 

heater power are displayed on the LCD display.

  The program of the balanced energy saving calculates the heater 

capacity required to maintain indoor air temperature with accuracy up to 1 °C 

and heating output control with accuracy up to 1%. 

  The air bypass damper is used for heat exchanger frost protection 

during low outside temperatures. In ventilation mode without heating the 

bypass damper is used to cut off supply air delivery and enable no heat 

recovery ventilation mode. 

  The control system monitoring program is used to track the operation 

parameters. In case of emergency like heater overheating, communication 

circuit break, the control system is cut off and the alarm information is 

displayed on the control panel. 

  The filter replacement warning is shown on the display with set 

periodicity. 

  All user settings are saved in the non-volatile storage of the control 

panel. 

The temperature sensors are supplied pre-wired.

The connections to the controller circuit board are shown in fig. 11. 

Terminal block on 

the control panel

yellow  

+

green  

В

brown  

А

white

Data cable

Socket connector for 

outdoor air temperature 

sensor

1
2
3
4

Socket connectors on 

the controller circuit 

board 

yellow  

1

green  

2

brown  

3

white  

4

CONTROLLER CIRCUIT BOARD 

WALL-MOUNTED CONTROL PANEL

Socket connector for 

supply air temperature 

sensor

Fig. 11. Control panel mounting 

Fig. 12. Control panel mounting 

UNIT CONTROL 

3

4

5

6

7

8

1

2

9

1. Control panel display.

2. The glowing red LED light indicates an alarm situation. The blinking red 

light indicates the need to replace the filter.  

3. Temperature sensor. 

4. «Up» button is used to select a menu item by moving upwards or to increase 

a current parameter.  

5. «Down» button is used to select a menu item by moving downwards or to 

decrease a current parameter.  

6. «Enter» button is used to select a parameter to be edited or to move one 

level down in a list (in the working window it means menu access). 

7. «Escape» button is used to move to a higher level up  (in the working 

window it means interface language editing).

8. «Power» button is used to operate the unit status (turned on/off). 

9. The green LED light indicates an operation status of the unit. The indicator 

glows during the heater shutdown and is off when the unit is off.

KOMFORT_LE_v2(2)_EN.indd   11

10.08.2015   12:00:46

Содержание KOMFORT LE Series

Страница 1: ...OPERATION MANUAL KOMFORT LE AIR HANDLING UNIT WITH HEAT RECOVERY KOMFORT_LE_v2 2 _EN indd 1 10 08 2015 12 00 42 ...

Страница 2: ...sign 4 Operating logic 4 Delivery set 5 Technical data 6 Mounting 10 Condensate drainage 11 Control panel mounting 11 Connection to power mains 12 Unit control 17 Troubleshooting and fault handling 18 Technical maintenance 19 Acceptance certificate 19 Connection certificate 19 Warranty card CONTENTS KOMFORT_LE_v2 2 _EN indd 2 10 08 2015 12 00 42 ...

Страница 3: ... Transportation of the unit is allowed by any vehicle provided the unit is transported in the original package and is protected against weather and mechanical damages Use hoist machinery for handling and transportation to prevent possible mechanical damages of the unit Fulfil the requirements for transportation of the specified cargo type during cargo handling operations Store the unit in a dry an...

Страница 4: ...e actuated at 90 C with manual restart The built in G4 extract cassette filter and F7 supply cassette filter provide efficient extract and supply air filtration The unit includes an integrated control system a multifunctional control panel with LCD display The delivery set includes a 10 m long cable for connection of the control panel to the unit For KOMFORT LE 350 3 LE600 4 unit the terminal bloc...

Страница 5: ...PM min 1 1150 1100 1100 1350 1650 1850 1100 1150 Sound pressure level at 3 m distance dB A 24 45 28 47 28 47 32 48 48 60 49 65 Transported air temperature C from 25 up to 55 from 25 up to 50 from 25 up to 50 from 25 up to 55 from 25 up to 45 from 25 up to 40 from 25 up to 45 from 25 up to 40 Casing material aluzinc aluzinc Insulation 25 mm mineral wool 25 mm mineral wool Extract filter G4 G4 Suppl...

Страница 6: ...100 119 111 KOMFORT LE500 3 996 403 954 149 1057 554 497 100 119 111 KOMFORT LE530 4 996 403 954 159 1057 554 497 100 119 111 KOMFORT LE600 4 996 403 954 199 1057 554 497 100 119 111 A C E F G B ØD H I K M L Model Dimensions mm A B C D E F G H I K L M KOMFORT LE800 9 1117 460 1071 249 1176 832 698 613 80 126 154 386 KOMFORT LE1200 9 1117 460 1071 249 1176 832 698 613 80 126 154 386 KOMFORT LE1700 ...

Страница 7: ...may reduce air flow The mounted air ducts must not be deformed Provide airtight connection of the air ducts to the unit spigots and fittings The unit mounting position must provide condensate drainage and access to the terminal box for electric connection and access to the service panel for maintenance and filter replacement While mounting install a ventilation grille an outer hood a disk valve or...

Страница 8: ...unting connect each unit to an individual U trap Direct condensate withdrawal with no connection to the drain system is not allowed Fig 7 Condensate drainage m in 3 drain pipe U trap sewage system connecting hose connecting hose min 3 А В А В 60 mm CONNECTION TO POWER MAINS WARNING Read the operation manual prior to any electric installations Connection of the unit to power mains is allowed by a q...

Страница 9: ...n is placed inside of the terminal box The terminal clamp marking corresponds to the marking on the wiring diagram Route the cables to the terminal box through the cable lead in on the unit side panel to preserve the electrical protection class The fixed electrical wiring must be equipped with an automatic switch that is used for connection of the unit to power mains with a gap on all poles at lea...

Страница 10: ...k 3 1 Remove the data cable 2 Route the cable to the control panel installation place 3 Install the control panel fig 10 as follows 3 1 Route the cable through the opening in the bottom cover 3 2 Fix the bottom cover of the control panel in the installation place The screw head must not be in contact with the control panel circuit board otherwise the equipment may be damaged 3 3 Strip the cable fo...

Страница 11: ...ck the operation parameters In case of emergency like heater overheating communication circuit break the control system is cut off and the alarm information is displayed on the control panel The filter replacement warning is shown on the display with set periodicity All user settings are saved in the non volatile storage of the control panel The temperature sensors are supplied pre wired The conne...

Страница 12: ...n mode confirmed by the blinking green LED light indicator and turns off in 2 minutes The parameters are selected and edited via the user menu see below Unit shutdown procedure Shutdown of electric heating elements Changeover to low speed and running with low speed for 2 minutes Activation of Heater blowing mode The green LED light is blinking This mode is used for cooling of the electric heating ...

Страница 13: ...m the main window press Temperature setting Service menu Speed stage Navigation between the menu items use the buttons press or press Back one level and entering the main window press Entering the current menu item for editing press 5 1 Main menu Is used to edit the most important operating parameters 5 1 1 Temperature setting Entering the menu item Temperature setting select the required item pre...

Страница 14: ...n of the warning signal from the control panel The factory setting is 99 days Entering the menu item Service menu select the required item press Temperature setting Service menu Speed stage Entering the menu item Filter replacement timer select the required item press Clock and calendar Day Timer Filter replacement timer Editing the time period set the required value Filter replacement after days ...

Страница 15: ...dule If this mode id activated the unit turns on in set time operates in compliance with set parameters with automatic fan speed and temperature control according to set parameters of week schedule Main window with activated week timer is displayed as follows room set Vent Н Heat Entering the menu item Service menu select the required item press Temperature setting Service menu Speed stage Enterin...

Страница 16: ...nger freezing this way In case of the heat exchanger freezing danger the bypass damper located in the supply air side is opened The supply air flows through the bypass damper and the extract air flows through the heat exchanger and heats and frozen heat exchanger surface After defrosting of the heat exchanger and increase of the extract air temperature the bypass damper os closed and the supply ai...

Страница 17: ...es not start when the unit is on No power supply or wrong connection to power mains Connect the unit to power mains Troubleshoot the connection error Jammed motor soiled impeller blades Remove the motor jam clean the impeller blades Automatic switch tripping Short circuit in power grid Turn the unit off and contact the unit seller for troubleshooting Low air flow Too low set speed Set higher speed...

Страница 18: ...at exchanger efficiency even in case of the regular filter cleaning Clean it with warm detergent solution Remove the heat exchanger from the unit and flush it with warm detergent solution Install the dry heat exchanger back to the unit 3 Fan maintenance once per year The regular filter cleaning may not completely prevent the dust ingress into the unit which results in the unit capacity decrease Cl...

Страница 19: ...ation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date ____________________ Company Name Date Signature The air handling unit with heat recovery KOMFORT LE350 3 KOMFORT LE500 3 KOMFORT LE530 4 KOMFORT LE600 4 KOMFORT LE800 9 KOMFORT LE1200 9 K...

Страница 20: ...www blaubergventilatoren de KOMFORT LE v 2 2 EN KOMFORT_LE_v2 2 _EN indd 20 10 08 2015 12 00 53 ...

Отзывы: