KB-200-5
38
B1
Superior controller
B2
Control unit of the capacity regulator
F1
Main fuse
F2
Compressor fuse
F3
Control circuit fuse
F4
Oil monitoring
F5
High pressure switch
F6
Low pressure switch
F8
Fan circuit breaker (fan 1)
F9
Fan circuit breaker (fan 2)
F13
Overload protective device "motor" PW1
F14
Overload protective device "motor" PW2
F17
Control transformer fuse
H1
Light "overtemperature (motor and discharge
gas)"
H2
Light "oil supply fault"
K1
Contactor "1st part winding"
K2
Contactor "2nd part winding"
K12
Coupling relay
K1T
Time relay "part winding start"
K2T
Time relay "start delay"
K11T
Time delay of compressor start for fan pre-
start
M1
Compressor
M3
Fan 1
M4
Fan 2
Q1
Main switch
R1-6
Temperature sensor in motor winding
R7
Discharge gas temperature sensor
R8
Oil heater
S1
Control switch
S2
Reset "overtemperature (motor and dis-
charge gas)"
S3
Reset "lack of oil"
T1
Transformer (example for 230 V)
Y1
Solenoid valve "start unloading"
Y2
Solenoid valve "liquid line"
Y3
Solenoid valve "capacity control"
Instead of the coupling relay, connect the optional
winter controller to the fan(s)
This description supplements the operating instructions
of the fan manufacturer with details on the electrical
connection of the winter controller. Mechanical and
electrical hazards may arise from the fans. Therefore,
please read the fan operating instructions carefully and
keep them available at the refrigeration system
throughout the lifetime of the condensing unit!
When working on the electrical system:
DANGER
Electric shock!
Electric charge > 50 μC! Life-threatening
voltages on fan connection cables even after
disconnecting the voltage supply!
After disconnecting the voltage, wait five
minutes before touching the cables. First short-
circuit the connection cables for N (blue), L
(black) and PE (green-yellow)!