Parameter value limits:
flue gases temperature rise, °С:
1-99;
MAX flame start-up time, minutes:
1-99.
Flue gases temperature rise values alarming about fire appearance in burner
firebox are entered in this window. Temperature difference is measured after flame
igniter actuation. Once temperature is increased to the setup value the Controller
transfers to the operating mode.
The second parameter is MAX flame start-up time (showed in minutes). This is a
period of time during which flue gases temperature shall rise (fuel ignition shall
happen). Once allocated time is completed the repeated flame start-up will take place.
To leave the flame start-up completion window move the cursor – frame to icon
«Back»,
, and press the encoder button, the Controller will go back to flame start-up
menu.
Picture 18 – Flame Start-Up Completion Window
4.2.3 Fuel Delivery
To enter the fuel delivery change window (Picture 19) it is required to select
menu item «Fuel Delivery»,
, in the flame start-up menu and press the button. The
current parameter value will be displayed in the popped up window.
To change parameter value, it is required to press the encoder button, the value
will change symbols color to red. By turning encoder set up the needed value and
confirm the entered value by pressing the button.