Fan Adjustment – maximum and minimum capacity of fan
operation is set up.
Cleanup – setup of parameters for firebox cleanup.
Capacity, % – used for setting up controller operation
parameters in manual mode. Allows presetting burner capacity
and hysteresis of exit from «Standby» mode.
Back – return to previous menu.
EXIT – return to the Controller main screen. It is not used
while selecting operation mode and burner startup, return to the
main screen is carried out automatically.
3.3.1 Internal Screw Operation Setting Up
To change internal screw operation parameters it is required to go to the menu
«PID mode settings» and select menu item «Internal Screw»,
, press the encoder
button – the window for setting up time of fuel delivery to the furnace will open
(Picture 10).
To change the value you shall press the encoder button – figures will change
their color to red, you set the needed parameter value and confirm it by repeatedly
pressing the encoder button – figures will return their color. Operation time is changed
within limits from 1 to 99 seconds.
To leave the internal screw setup window, move the cursor - frame to icon
«Back»,
, and press the encoder button, the Controller will go back to menu « PID
mode settings».