VI.e)
Room regulator
This function allows to set the operating parameters of room regulator which is connected to the pellets-fired boiler
controller. It is necessary to launch room regulator which is connected by choosing the necessary room regulator
type. Up to three room regulators can be connected to the controller.
VI.e.1)
TECH RS regulator
Select this option if you want to connect room regulator with RS interface. Such regulator lets the user to review the
current CH boiler parameters and to change certain settings, e.g. advance CH boiler temperature, advance DHW
temperature.
VI.e.2)
Standard regulator 1 / Standard regulator 2
Select this option if you connect the regulator of two technical conditions. Such regulator sends a signal to the main
controller and indicates whether the room temperature was achieved or not.
VI.e.3)
Room regulator CH pump
If this function is activated, the CH pump is deactivated when the room regulator sends a signal notifying about the
reached room temperature.
VI.f)
Time settings
This function is used to set the desired time. This setting is important for the weekly control in order for the device to
function properly.
VI.f.1)
Clock settings
This function is used to set the current time.
VI.f.2)
Date settings
This function is used to set the current date.
VI.g)
Fuel level calibration
After the proper performance of fuel level calibration, the user can review the current fuel level in the controller’s
screen. During the first step, the fuel is filled to the fuel tank and the option “
Fuel tank full” is selected.
The
controller remembers this level (100%).
When no fuel is left in the fuel tank after a certain period of time of CH boiler operation, the user shall
choose the option “
Fuel tank empty
”. This allows the fuel tank to be calibrated and the controller automatically
informs the user on the current fuel level. When the fuel level desk is chosen in the main screen, the monitor shows
the set amount of the remaining fuel (%) and the forecasted time for the consumption of fuel (days and hours).
Such calibration is usually performed once. When the fuel tank is filled again, it is enough to select option
“
Fuel tank full”
in the user menu.
VI.h)
External temperature correction
This function allows the calibration of the external sensor.
VI.i)
GSM module
NOTE
This control type is applied in case of acquisition and connection of additional control module
ST-65 which
is not included in the standard controller set
.
GSM module is a selected device which communicates with another controller and lets the user to control CH boiler
with a mobile phone (remotely). The user sends SMS each day when the alarm goes on. Furthermore, after sending
the text report, the user receives
26