Opening time
•
Type of valve
•
CH
•
floor
•
Room regulator
•
Control without room regulator
•
RS regulator - reduction
•
RS regulator - proportional
•
Standard regulator
•
Air basis control
•
Valve pump
•
Always turned on
•
Always turned off
•
Turned on above the threshold valve
•
Turn on temperature
•
Reverse flow protection
•
ON
•
OFF
•
Minimum temperature
•
Single stroke
•
Minimum opening
•
Proportionality coefficient
•
CH sensor option
•
CH sensor
•
Additional sensor 1
•
Sensor option
•
Calibration
•
Measurement stopping
•
Factory settings
•
Valve dismantlement
VI.c.1)
Registration
In case of additional valves, it is necessary to register the valve by entering the number of module (indicated on the
module frame, e.g.: ST-431N) in order to configure its parameters.
VI.c.2)
Valve activation/deactivation
This function allows the user to deactivate the control.
VI.c.3)
Pre-set valve temperature
This parameter defines the necessary temperature to be maintained by the valve. In case of proper operation, the
water temperature behind the valve comes closer to the pre-set value.
VI.c.4)
Opening time
This parameter defines the time necessary for the valve solenoid to open the valve in the 0% to 100% position. This
valve should be adjusted by the value according to solenoid nominal value.
VI.c.5)
Type of valve
With this parameter the user selects the type of controlled valve:
19