NCR-80 Four-wire 4-20 mA/HART
925-0332 Rev B
6 Set up the sensor with the display and adjustment module
33
6 Set up the sensor with the display and ad-
justment module
6.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor and removed again at any
time. You can choose any one of four different positions - each displaced by 90°. It is not neces
-
sary to interrupt the power supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module on the electronics in the desired position and turn
it to the right until it snaps in.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an additional connection is not
necessary.
Fig. 30: Installing the display and adjustment module in the double chamber
housing
Note:
If you intend to retrofit the instrument with a display and adjustment module for continuous mea
-
sured value indication, a higher lid with an inspection glass is required.