NCR-80 Four-wire 4-20 mA/HART
925-0332 Rev B
5 Connecting to power supply and bus system
31
5.3 Wiring plan, double chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d-ia version.
Fig. 27: Electronics compartment, double chamber housing
1 Internal connection to the terminal compartment
2 For display and adjustment module or interface adapter
Information:
The connection of an external display and adjustment unit is not possible with the Ex-d-ia ver-
sion.
Fig. 28: Connection compartment with double chamber housing with mains voltage
Terminal
Function
Polarity
1
Voltage supply
+/L
2
Voltage supply
-/N
4 ... 20 mA output (active)
+
6
4 ... 20 mA output (passive)
+
7
Mass - output
-
8
Function ground when installing ac-
cording to CSA (Canadian Standards
Association)