USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx
27
2.4.4. DC1005 Panel cutout
CAUTION
Installation instruction:
Only install the Dialog-Controller on a level surface!
The support points on the Dialog-Controller may not deviate from one another
by more than +/-0.5 mm. If the Dialog-Controller is nonetheless mounted on a
base which is not level, mechanical tension can result in cracks in the front
panel.
The Dialog-Controller is intended for front installation. A square panel cutout is required. The support mate-
rial thickness may not exceed 6 mm. The panel cutouts are identical for units equipped with either a key-
board or a touchpad.
2VF100235DG00.cdr
2.4.5. Mounting regulation DC1005
The Dialog-Controllers are designed for automatic convection cooling.
The Dialog-Controllers must be mounted vertically onto a metallic mounting plate.
WARNING
Danger of overheating and fire!
The Dialog-Controller may be destroyed even at a permissible ambient tem-
perature if the convection cooling cannot function because it is built-in.
It must therefore be installed vertically and the upper and lower housing aper-
tures must not be covered over!
DANGER OF
OVERHEATING
AND FIRE!
Vertical
installation
Frontansicht
Front view
Fronttafel-Ausschnitt
184 x 162
front panel cut out
Frontrahmen / front frame
194 x 172
0
3
3
1
4
14
148
159
162
1
7
0
1
8
1
1
8
4
0
Bohrungen /
5 mm (4x)
drills
Ø
Alle Maße in [mm]
All dimensions in [mm]