8
Bentone
!
Scale value applies to
0 mbar furnace pressure.
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
16,0
18,0
20,0
22,0
15
20
25
30
35
40
45
50
55
160303-291-2
kW
Air settings
Nozzle assembly
Scale
Burner output
2.5
Basic settings - Fuel oil
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
16,0
18,0
20,0
22,0
15
20
25
30
35
40
45
50
55
160303-432
kW
Air settings
Nozzle assembly
Scale
Burner output
2.6
Basic settings - HVO/XTL
!
Scale value applies to
0 mbar furnace pressure.
Flame signal
When operating at high power or low air excess and HVO/XTL is used as fuel,
the flame signal may deteriorate (blue flame), the signal lamp in the reset
button flashes green.
By lowering the air velocity or changing the flame detector to QRC1 A1, the
flame signal can be improved.